Table 3, Protective safety limits and control settings, N in – Carrier 17/19EX User Manual
Page 300

Table 3 — Protective Safety Limits and Control Settings
Monitored Parameter
Limit
Applicable Comments
Temperature Sensors Out
Of Range
–40 to 245 F (–40 to 118.3 C)
Must be outside range for 2 seconds
Pressure Transducers Out
Of Range
0.08 to 0.98 Voltage Ratio
Must be outside range for 2 seconds.
Ratio = Input Voltage ÷ Voltage Refer-
ence
Compressor Discharge
Temperature
>
220 F (104.4 C)
Preset, alert setting configurable
Motor Winding Temperature
>
220 F (104.4 C)
Preset; alert setting configurable
Bearing Temperature
>
220 F (104.4 C)
Preset; alert setting configurable
Evaporator Refrigerant
Temperature (Temp
converted from Pressure
Reading)
<
33 F (for water chilling) (0.6° C)
Preset; configure chilled medium for
water (Service1 table)
<
Brine Refrigerant Trippoint (set point
adjustable from 0 to 40 F [–18 to 4 C]
for brine chilling)
Configure chilled medium for brine
(Service1 table). Adjust brine refrigerant
trippoint for proper cutout
Transducer Voltage
<
4.5 vdc
>
5.5 vdc
Preset (Read voltage at terminals 34
and 35 on PSIO module)
Condenser Pressure – Switch
– Control
>
218 psig ± 7 psig (1503 ± 48 kPa),
reset at 120 ± 10 (827 ± 69 kPa)
Preset
215 psig (1482 kPa)
Preset
Oil Pressure
– Switch
– Control
Cutout
<
11
psid (76 kPad) ± 1.5 psid
(10.3 kPad) Cut-in > 16.5 psid (114
kPad) ± 4 psid (27.5 kPad)
Preset, no calibration needed
Cutout
<
15 psid (103 kPad)
Alert < 18 psid (124 kPad)
Preset
Line Voltage —
High
—
Low
—
Single-cycle
>
110% for one minute
Preset, based on transformed line volt-
age to 24 vac rated-input to the Starter
Management Module. Also monitored at
PSIO power input.
<
90% for one minute and
≤
85% for 3
seconds
<
50% for one cycle
Compressor Motor Load
(% Compressor Amps)
>
110% for 30 seconds
Preset
<
10% with compressor running
Preset
>
10% with compressor off
Preset