Table 13 — additional cooler weights, Table 13 – Carrier 17/19EX User Manual
Page 337

NIH — Nozzle-In-Head
* When using a machine configuration other than 2-pass, NIH waterboxes with 150 psig (1038 kPa)
covers, add the weights listed in this table to the appropriate weights in
to obtain the correct
cooler weight.
Table 13 — Additional Cooler Weights*
Component
Waterbox
Type
Number
of
Passes
Design
Maximum
Water Pressure
Additional
Dry Weight
Additional
Water Weight
psig
kPa
lb
kg
lb
kg
Condenser
NIH
1, 3
150
1034
515
234
-
-
NIH
1, 3
300
2068
2941
1334
-
-
NIH
2
300
2068
2085
946
-
-
Marine
1, 3
150
1034
2100
953
5102
2314
Marine
2
150
1034
792
359
2551
1157
Marine
1, 3
300
2068
3844
1744
5102
2314
Marine
2
300
2068
2536
1150
2551