A. shutdown with on/off/reset-off – Carrier 17/19EX User Manual
Page 310

LEGEND For Table 8, A - N
1CR AUX
— Compressor Start Contact
OILPD
— Oil Pressure
CA P
— Compressor Current
OILT
— Oil Sump Temperature
CDFL
— Condenser Water Flow
PIC
— Product Integrated Control
CHIL S S
— Chiller Start/Stop
PRS TRIP
— Pressure Trip Contact
CMPD
— Discharge Temperature
PSIO
— Processor Sensor Input/Output Module
CRP
— Condenser Pressure
RLA
— Rated Load Amps
ERT
— Evaporator Refrigerant Temperature
RUN AUX
— Compressor Run Contact
EVFL
— Chilled Water Flow
SMM
— Starter Management Module
GV TRG
— Target Guide Vane Position
SPR PL
— Spare Protective Limit Input
LID
— Local Interface Device
STR FLT
— Starter Fault
MTRB
— Bearing Temperature
TXV
— Thermostatic Expansion Valve
MTRW
— Motor Winding Temperature
V P
— Line Voltage: Percent
V REF
— Voltage Reference
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
A. Shutdown with ON/OFF/RESET-OFF
Primary Message
Secondary Message
Probable Cause/Remedy
Manually Stopped —
Press
CCN or Local to Start
PIC in OFF mode; press the CCN or local softkey to
start unit.
Terminate Pumpdown
Mode
To Select CCN or Local
Enter the Control Test table and select Terminate Lock-
out to unlock compressor.
Shutdown In Progress
Compressor Unloading
Machine unloading before shutdown due to Soft Stop
feature.
Shutdown In Progress
Compressor Deenergized
Machine compressor is being commanded to stop.
Water pumps are deenergized within one minute.
Ice Build
Operation Complete
Machine shutdown from Ice Build operation.