J. out-of-range sensor failures – Carrier 17/19EX User Manual
Page 320

Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
J. Out-of-Range Sensor Failures
Primary Message
Secondary Message
Alarm Message/Primary
Cause
Additional Cause/
Remedy
Sensor Fault
Leaving CHW Tempera-
ture
Sensor Fault: Check leaving CHW
sensor.
See
sensor test procedure
and check sensors for
proper operation and
wiring.
Sensor Fault
Entering CHW Tempera-
ture
Sensor Fault: Check entering
CHW sensor.
Sensor Fault
Condenser Pressure
Sensor Fault: Check condenser
pressure transducer.
Sensor Fault
Evaporator Pressure
Sensor Fault: Check evaporator
pressure transducer.
Sensor Fault
Bearing Temperature
Sensor Fault: Check bearing tem-
perature sensor.
Sensor Fault
Motor Winding Temp
Sensor Fault: Check motor tem-
perature sensor.
Sensor Fault
Discharge Temperature
Sensor Fault: Check discharge
temperature sensor.
Sensor Fault
Oil Sump Temperature
Sensor Fault: Check oil sump tem-
perature sensor.
Sensor Fault
Oil Pressure Transducer
Sensor Fault: Check oil pressure
transducer.