Heat pump equipment wiring – Braeburn 140404 User Manual

Page 9

background image

Heat Pump Equipment Wiring

3.6

NOTE: For Conventional Systems, see Section 3.5
Connect a single or multi-stage heat pump system to the zone panel as shown. A conventional thermostat
may be used with a heat pump system, however, emergency heat will be controlled by the panel emergency
heat switch or the optional remote emergency heat switch. For a single stage system, the auxiliary heat
control is not used.

ALWAYS PROVIDE DISCONNECT AND OVERLOAD PROTECTION AS REQUIRED

1 HEAT / 1 COOL - No Auxiliary Heat

Set Equipment Type to SSH

Rh 24 VAC Power (Heating Transformer)

Rc Connected to Rh with Jumper

O/B Changeover Valve [Note 4]
Y1
Compressor Call (1st Stage Heating/Cooling)
G

Fan Call

C

24 VAC Transformer Common

2 HEAT / 2 COOL - No Auxiliary Heat

Set Equipment Type to MSH

Rh 24 VAC Power (Heating Transformer)

Rc Connected to Rh with Jumper

O/B Changeover Valve [Note 4]

L

Optional System Fault Monitor

Y1 Compressor Call Stage 1 (1st Stage Heating/Cooling)
Y2 Compressor Call Stage 2 (2nd Stage Heating/Cooling)
G

Fan Call

C

24 VAC Transformer Common

2 HEAT / 1 COOL - With Auxiliary Heat

Set Equipment Type to MSH

Rh 24 VAC Power (Heating Transformer)

Rc Connected to Rh with Jumper

O/B Changeover Valve [Note 4]

L

Optional System Fault Monitor

W2 Auxiliary Heat Relay (2nd Stage Heating) [Note 5]
Y1
Compressor Call Stage 1 (1st Stage Heating/Cooling)
E Emergency Heat Call
G

Fan Call

C

24 VAC Transformer Common

3 HEAT / 2 COOL - With Auxiliary Heat

Set Equipment Type to MSH

Rh 24 VAC Power (Heating Transformer)

Rc Connected to Rh with Jumper

O/B Changeover Valve [Note 4]
L

Optional System Fault Monitor

AX1 Auxiliary Heat Relay (3rd Stage Heating)
Y1 Compressor Call (1st Stage Heating/Cooling)
Y2 Compressor Call (2nd Stage Heating/Cooling)

E

Emergency Heat Call

G

Fan Call

C

24 VAC Transformer Common

9

4 HEAT / 2 COOL - With Auxiliary Heat

Set Equipment Type to MSH

Rh 24 VAC Power (Heating Transformer)

Rc Connected to Rh with Jumper

O/B Changeover Valve [Note 4]

L

Optional System Fault Monitor

AX1 Auxiliary Heat Relay (3rd Stage Heating)
AX2 Auxiliary Heat Relay (4th Stage Heating)
Y1 Compressor Call (1st Stage Heating/Cooling)

Y2 Compressor Call (2nd Stage Heating/Cooling)

E

Emergency Heat Call

G

Fan Call

C

24 VAC Transformer Common

NOTES

[4] O (cool active) or B (heat active) is selected in the installer

settings menu.

[5] Install a field supplied jumper between the W2/AX2 and

W1/E/AX1 terminals if there is no separate emergency heat

relay installed.