No. Installer Setting
Display
Factory
Setting
Comments
(
Notes follow table)
Indicator
Default
Options
(More information follows this table)
11 Short Cycle Protection
SCP
5
5 to 0
Selects a compressor short cycle protection delay of 5,
4, 3, 2 or zero minutes after a compressor call
12 Outdoor Sensor Compressor
COM BAL NO
NO
Disables Compressor Balance Point Control
Balance Point
0 to 50
Selects a Compressor Balance Point of 0 to 50° F
[Note 1, 2]
13 Outdoor Sensor Auxiliary
AUX BAL NO
NO,
Disables Auxiliary Heat Balance Point Control
Heat Balance Point
40 to70 Selects an Auxiliary Heat Balance Point of 40 to 70° F
[Note 1, 2]
14 Equipment Staging
STAGING ZON
ZON
Select to stage on number of zones calling (Setting 15)
TIM
Select to stage on Zone Panel Timer
TST
Select to stage on Thermostat Staging Calls
[Note 8]
15 Equipment Staging Lock
STAGLOK 2
2 - # of
Selects the number of zones that must call before the
zones
equipment will upstage Zone Count (setting 14 = ZON)
16 Second Stage Fan Control
G2 FAN ZON
ZON
Select to Turn on Second Stage Fan on number of calling
zones (Setting 17)
STG
Select to Turn on Second Stage Fan when second stage
is activated
17 Second Stage Fan
G2 ZONES 2
2 - # of
Select the number of zones that must call before the
zones
second stage fan will turn on
18 Priority Zone
PRIORTY 1
OFF
Select to have opposite calls answered in any zone
1 to 4
Select zone 1 to 4 to limit calls so equipment will only
service call matching last call of zone 1-4
19 Opposite Mode Timer
OP MODE 15
15 to 60
Select the number of minutes to delay system changeover
when zones are calling for heat and others zones are
calling for cooling.
20 Zone to Activate
EM HEAT 1
NO
Select to allow Emergency Heat from Thermostats
Emergency Heat
1 to 4
Select to match the Zone on the main panel allowed to
call emergency heat.
[Note 3]
21 Fire Alarm
FIRE ALM NI
NI
Select for a normally inactive (Open) fire relay
Normal Active /
NA
Select for a normally active (Closed) fire relay
Normal Inactive
[Note 4]
12
NOTES - Configuration
[1] Only available if MSH system type is selected.
[2] Only available if outdoor sensor is connected.
[3] Thermostat type must be heat pump.
[4] All equipment and fans will shut down and all dampers will power close
[5] Disable will not show plenum temperature and will prevent staging by temperature.
[6] Only available if supply air sensor is enabled.
[7] O/B selection on equipment must match thermostat O/B selection.
[8] Multi-stage thermostats must be used.
[9] Set thermostats to conventional.