No. Installer Setting

Display

Factory

Setting

Comments

(

Notes follow table)

Indicator

Default

Options

(More information follows this table)

11 Short Cycle Protection

SCP

5

5 to 0

Selects a compressor short cycle protection delay of 5,

4, 3, 2 or zero minutes after a compressor call

12 Outdoor Sensor Compressor

COM BAL NO

NO

Disables Compressor Balance Point Control

Balance Point

0 to 50

Selects a Compressor Balance Point of 0 to 50° F

[Note 1, 2]

13 Outdoor Sensor Auxiliary

AUX BAL NO

NO,

Disables Auxiliary Heat Balance Point Control

Heat Balance Point

40 to70 Selects an Auxiliary Heat Balance Point of 40 to 70° F

[Note 1, 2]

14 Equipment Staging

STAGING ZON

ZON

Select to stage on number of zones calling (Setting 15)

TIM

Select to stage on Zone Panel Timer

TST

Select to stage on Thermostat Staging Calls

[Note 8]

15 Equipment Staging Lock

STAGLOK 2

2 - # of

Selects the number of zones that must call before the

zones

equipment will upstage Zone Count (setting 14 = ZON)

16 Second Stage Fan Control

G2 FAN ZON

ZON

Select to Turn on Second Stage Fan on number of calling

zones (Setting 17)

STG

Select to Turn on Second Stage Fan when second stage

is activated

17 Second Stage Fan

G2 ZONES 2

2 - # of

Select the number of zones that must call before the

zones

second stage fan will turn on

18 Priority Zone

PRIORTY 1

OFF

Select to have opposite calls answered in any zone

1 to 4

Select zone 1 to 4 to limit calls so equipment will only

service call matching last call of zone 1-4

19 Opposite Mode Timer

OP MODE 15

15 to 60

Select the number of minutes to delay system changeover

when zones are calling for heat and others zones are

calling for cooling.

20 Zone to Activate

EM HEAT 1

NO

Select to allow Emergency Heat from Thermostats

Emergency Heat

1 to 4

Select to match the Zone on the main panel allowed to

call emergency heat.

[Note 3]

21 Fire Alarm

FIRE ALM NI

NI

Select for a normally inactive (Open) fire relay

Normal Active /

NA

Select for a normally active (Closed) fire relay

Normal Inactive

[Note 4]

12

NOTES - Configuration

[1] Only available if MSH system type is selected.
[2] Only available if outdoor sensor is connected.
[3] Thermostat type must be heat pump.
[4] All equipment and fans will shut down and all dampers will power close
[5] Disable will not show plenum temperature and will prevent staging by temperature.
[6] Only available if supply air sensor is enabled.
[7] O/B selection on equipment must match thermostat O/B selection.
[8] Multi-stage thermostats must be used.
[9] Set thermostats to conventional.