1
Specifications 2 Installation and Wiring 3 Quick Reference
4 Installer Settings 5 System Testing
To prevent damage to the thermostat, never use a sharp instrument
to press the touchscreen keys. Always press keys with your fingers.
Attention
• Possible electric shock or damage to equipment can occur.
• Disconnect power before beginning installation.
Caution
This thermostat requires 24 Volt AC Power or 2 properly installed “AA” Alkaline batteries for
proper operation. When connecting 24 Volt AC Power the batteries may be installed as a backup.
For use only as described in this manual. Any other use will void warranty.
6100 Single Stage Heat / Cool Conventional
or Heat Pump
6300 Up to 4 Heat / 2 Cool Heat Pump
Up to 3 Heat / 2 Cool Conventional
6400 Up to 4 Heat / 2 Cool Heat Pump
Up to 3 Heat / 2 Cool Conventional
with Humidity Control
Warning
For installation by experienced service technicians only.
®
6000-100-05B
Installer Guide
Touchscreen
®
This thermostat is compatible with:
• Single stage heat / cool conventional and heat pump systems
• Conventional systems up to 3 stages of heating and 2 stages of cooling (6300/6400 only)
• Heat pump systems up to 4 stages of heating and 2 stages of cooling (6300/6400 only)
• 250 – 750 millivolt heating only systems
Electrical and control specifications:
• Electrical Rating: 24 Volt AC
• 1 amp maximum load per terminal
• AC Power: 18 – 30 Volts AC
• DC Power: 3.0 Volt DC (2 “AA” Alkaline
Batteries Included)
• Control Range: 45° – 90° F (7° – 32° C)
• Temperature Accuracy: +/- 1° F (+/- .5° C)
• Outdoor Temperature Display Range:
-40° - 120° F (-40° - 49° C)
Humidification Specifications (6400 Only)
• Humidification Control Range: 10% - 50% RH
• Dehumidification Control Range: 40% - 80% RH
1 Specifications
Terminations
• 6100: G, Rc, Rh, W, O/B, Y, C, S1, S2
• 6300: A, G, Rc, Rh, W1/E/AUX1, W2/AUX2, W3/O/B,
Y1, Y2, C, L, S1, S2
• 6400: H, A/D, G, Rc, Rh, W1/E/AUX1, W2/AUX2, W3/O/B,
Y1, Y2, C, L, S1, S2