System Checkout

5

After the wiring and configuration is complete, built in automatic zone panel tests may be used to verify
equipment, damper, and panel operation.
To start the panel Test Mode:
1.
Ensure all wiring is complete and power has been applied to the main and expansion panels
2. Press TEST for 3 seconds and release
3. Press SELECT to turn the test on and off
4. Press NEXT to move on to the next test
5. Press HOLD FOR EXIT for 3 seconds to exit test mode

The following tests are available in Test Mode:

Expansion Panel Zone Communication Test
(only if expander panels are connected)
This test will confirm or add expansion stages to the main zone
panel. Each recognized zone is shown from the lowest to the
highest number by pressing the select key. If a zone is
communicating properly, the display will show the zone number
and OK. If the zone is not communicating properly, the display
will show “Address Invalid” or “Duplicate Address”. See Error
Conditions, section 7 for help troubleshooting. Press

SELECT

to Test or

NEXT to advance to the next test.

Heating Stage(s) Test ON or OFF
This test turns on all heating stages (including O-B for heat pump
configurations) the system fan, and commands all dampers to
open. The heating stages will by energized by the type of system
configured in the installer settings. A heat pump configuration
will have all compressor calls and Auxiliary Heat. A conventional
configuration will call all conventional heating stages.
Press

SELECT to Test or NEXT to advance to the next test.

Cooling Stage(s) Test ON or OFF
This test turns on all cooling stages (including O-B for heat pump
configurations), the system fan, and also commands all dampers
to open. Press

SELECT to Test or NEXT to advance to the next test.

13