Braeburn 3200 User Manual
Warning, Premier series, Non-programmable thermostats
©2011 Braeburn Systems LLC • All Rights Reserved. 3000-100-010
1
WARNING
Important Safety Information
Premier Series
Non-Programmable Thermostats
Specifications
Installation
Testing Your New Thermostat
Programming User Settings
Temperature Adjustment
1
2
3
4
5
1
Specifications
• Electrical Rating: 24 Volt AC (18-30 Volt AC)
1 amp maximum load per terminal
2 amp total maximum load (all terminals) (Model 3000)
3 amp total maximum load (all terminals) (Model 3200)
• Control Range: 45˚ - 90˚ F (7˚ - 32˚ C)
• Accuracy: +/- 1˚ F (+/- .5˚ C)
• AC Power: 18-30 Volt AC
• DC Power: 3.0 Volt DC (2 AA Alkaline batteries included)
Additional Operation
Features
Battery Replacement
Trouble Shooting
Wiring Diagrams
6
7
8
9
• Always turn off power to the air conditioning or heating system prior to
installing, removing, cleaning or servicing thermostat.
• This thermostat requires either 24 Volts AC Power or two (2) properly installed
“AA” alkaline batteries for normal operation and control of the heating or
cooling system.
• This thermostat should only be used as described in this manual. Any other
use is not recommended and will void the warranty.
Specifications
1
•
Model 3000: Compatibility with low voltage single stage gas, oil or electric
heating or cooling systems, including single stage heat pumps; can also
be used on 250mv to 750mv millivolt heating only systems.
•
Model 3200: Compatibility with low voltage multi-stage gas, oil or electric
heating or cooling systems, including multi-stage heat pumps.
•
Terminations, Model 3000: Rc, Rh, B, O, Y, W, G, C
Terminations, Model 3200: R, O, B, C, Y1, Y2, E/W1, W2, G, L
cont.
Replacing Existing Thermostat
Installation
2
1. Always turn off power to the air conditioning or heating system prior to
removing existing thermostat.
2. Remove the cover of your old thermostat and locate the wire terminals.
Do not remove wires from terminals until step 3 is completed.
3. Using small pieces of masking tape, label wires prior to removal from
terminals. Use the chart below to determine the new terminal designations
for your new thermostat.
Old Terminal from
Existing Thermostat
New Terminal for
New Thermostat
(Model 3000)
New Terminal for
New Thermostat
(Model 3200)
Terminal
Description
V or Rc
Rc
Cooling
Transformer
M, 4, Rh, or R
Rh
Heating
Transformer
R, V-VR or VR-R
R
24 VAC
G or F
G
G
Fan Control
H, W or 4
W
Heating Control
W1, W2, W-U or E
E/W1
Emergency Heat /
1st Stage Heat
W2
W2
2nd Stage Heat
Y
Y
Cooling Control
Y, Y1 or M
Y1
1st Stage
Compressor
Y2
Y2
2nd Stage
Compressor
B
B
B
Reversing Valve
(Heating)
O
O
O
Reversing Valve
(Cooling)
C
C
C
24 VAC Common
L or X
L
System Status LED
4. After labeling and removing all wires from terminals, unscrew the existing
thermostat sub-base from wall. Secure wires to prevent them from slipping into
the hole in the wall.
MODEL
3000
MODEL
3200
Multi-Stage 2 Heat / 2 Cool
Conventional and Heat Pump
Single Stage Heat / Cool
Conventional and Heat Pump
Before Installing, Programming or Operating,
PLEASE READ ALL INSTRUCTIONS