Number of Fan Calls currently being serviced. Check the panel 
LED if it is necessary to determine exactly which zones are 
calling for Fan Operation.
16
Equipment Plenum Temperature is displayed. When the included 
plenum air temperature sensor is installed, the zone panel will 
display the Plenum temperature in the range of 30 - 200˚ F. 
Plenum Temperatures outside this range indicate an equipment error. 
See Section 7 Error Conditions for a further explanation. 
NOTES: When no zones are calling, the panel will command 
all dampers to open. 
• For maximum energy conservation, a purge will occur at the 
 end of each call. 
• No calls will be answered until the purge is complete. 
• Equipment staging is automatic based on time and plenum 
 temperature. 
• Dampers will not close and staging will not occur if the plenum 
 temperature sensor is enabled but not connected or 
 functioning properly. 
Emergency Heat Selection (Multi-stage Heat Pump Systems Only)
Emergency Heat can be selected at the main panel or from a Heat Pump Thermostat wired to the main panel.
No cooling calls will be answered if emergency heat is switched on.
To select Emergency Heat from the main panel:
1. Press and release the EM HEAT button located below the main display.
2. The display will update from HEAT CALLS to EM HEAT CALLS and will show COOL DISABLE to indicate that 
 no compressor calls will be answered.
3. To stop Emergency Heat, press the EM HEAT button again.
4. The display will update from EM HEAT CALLS to HEAT CALLS and COOL CALLS will return.
To select Emergency Heat from a thermostat
1. Set Emergency Heat Thermostat to Emergency Heat switch position (only one thermostat can 
 control Emergency Heat)
2. Raise heat setting on Emergency Heat Thermostat to create Emergency Heat call.
3. The zone panel display will update from HEAT CALLS to EM HEAT CALLS and will show COOL DISABLE to 
 indicate that no compressor calls will be answered.
4. To stop Emergency Heat, set the Emergency Heat Thermostat to a non-emergency heat position or 
 lower the temperature on the Emergency Heat Thermostat to end the emergency heat call. 
5. The zone panel display will update from EM HEAT CALLS to HEAT CALLS and COOL CALLS. 
NOTE: Configuration setting number 20 in section 4 selects which thermostat is used to activate Emergency Heat.