Expandable zone panel wiring terminals, Terminal qty. function description – Braeburn 140404 User Manual

Page 5

background image

EM HEAT

R

Y1
Y2

W1/E/AX1

W2/AX2

O/B/W3

G

L

C

THERMOST

AT

Z

ONE

1

PO

COMM

PC

DAMPER ZONE

1

R

Y1
Y2

W1/E/AX1

W2/AX2

O/B/W3

G

L

C

THERMOS

TAT

Z

ONE

2

DAMPER ZONE

2

PO

COMM

PC

R

Y1
Y2

W1/E/AX1

W2/AX2

O/B/W3

G

L

C

THERMOST

AT

Z

ONE

3

PO

COMM

PC

DAMPER ZONE

3

24V

24C

POWER 24

VA

C

EXP

ANSION

COM1
COM2
GND
COM3
COM4

EXP

ANSION

COM1
COM2
GND
COM3
COM4

R
Y1
Y2
W1/E/AX1
W2/AX2
O/B/W3
G
L
C

T

HERMOS

TAT

Z

ONE

4

PO

COMM
PC

DAMPER ZONE

4

Rh
Rc
Y1
Y2
G
G2
W1/E/AX1
W2/AX2
W3/O/B
L
C

E

QUIPMENT

FA1
FA2

FIRE

ALARM

SENSORS

SA1
SA2

ODT1
ODT2

SENSORS

Terminal Qty. Function Description

PANEL

24V

1

INPUT

24 VAC Transformer Power 100 VA Maximum

POWER

24C

1

INPUT

24 VAC Transformer Common

DAMPERS

PO

4

OUTPUT

24 VAC Power Open Zone Damper Terminal

COMM

4

OUTPUT

Zone Damper Common Terminal

PC

4

OUTPUT

24 VAC Power Close Zone Damper Terminal

SUPPLY

SA1

1

INPUT

Plenum Supply Air Sensor Terminal 1 (No Polarity)

AIR

SA2

1

INPUT

Plenum Supply Air Sensor Terminal 2 (No Polarity)

OUTDOOR

ODT1

1

INPUT

Outdoor Air Sensor Terminal 1 (No Polarity)

AIR

ODT2

1

INPUT

Outdoor Air Sensor Terminal 2 (No Polarity)

FIRE

FA1

1

INPUT

Normally Closed or Open Dry Pair (No Polarity)

ALARM

FA2

1

INPUT

Normally Closed or Open Dry Pair (No Polarity)

EXPANSION

COM1

2

PANEL

Expander Panel Communication

COM2

2

PANEL

Expander Panel Communication

GND

2

PANEL

Expander Panel Communication Ground

COM3

2

PANEL

Expander Panel Communication

COM4

2

PANEL

Expander Panel Communication

EQUIPMENT

Rh

1

INPUT

24 VAC Equipment Transformer Power Connection

Rc

1

INPUT

24 VAC Cooling Equipment Transformer (Dual Transformer Systems Only)

Y1

1

OUTPUT

1st Stage Compressor

Y2

1

OUTPUT

2nd Stage Compressor

G

1

OUTPUT

1st Stage Fan Control

G2

1

OUTPUT

2nd Stage Fan Control

W1/E/AX1

1

OUTPUT

[W1] 1st Stage Conventional Heat [E] Emergency Heat [AX1] 1st Stage Auxiliary Heat

W2/AX2

1

OUTPUT

[W2] 2nd Stage Conventional Heat [AX2] 2nd Stage Auxiliary Heat

W3/O/B

1

OUTPUT

[W3] 3rd Stage Conventional Heat [O] Cool Active Reversing Valve

[B] Heat Active Reversing Valve

L

1

INPUT

System Malfunction Indicator

C

1

INPUT

24 VAC Transformer Common

THERMOSTAT

R

4

OUTPUT

24 VAC Thermostat Power

Y1

4

INPUT

1st Stage Compressor Call

Y2

4

INPUT

2nd Stage Compressor Call

W1/E/AX1

4

INPUT

[W1] 1st Stage Conventional Heat Call [E] Emergency Heat Call

[AX1] 1st Stage Auxiliary Heat Call

W2/AX2

4

INPUT

[W2] 2nd Stage Conventional Heat Call [AX2] 2nd Stage Auxiliary Heat Call

O/B/W3

4

INPUT

[O] Cool Active Reversing Valve Call [B] Heat Active Reversing Valve Call

[W3] 3rd Stage Conventional Heat Call

G

4

INPUT

Fan Call

L

4

OUTPUT

System Malfunction Indicator

C

4

OUTPUT

24 VAC Transformer Common

RESET BUTTON

Press once to restart panel

Hold for 5 seconds to reset panel and restore all factory defaults

Rc/Rh TERMINAL JUMPER (J1)

Open jumper for dual transformer installations

WIRE STRIP GUIDE

Wires should be stripped 3/8 inch minimum

EXPANDABLE ZONE PANEL WIRING TERMINALS

5

1

2

3

4

5

6

7

8

9

10

11