beautypg.com

Bcm modbus and address assignments, 1 bcm modbus communication & support requirements, 1 function codes – AERCO Modulex E8 Controls Guide User Manual

Page 93: 2 modbus support requirements, Gf-115-c

background image

PR1: 02/23/12 Page 93 of 112

GF-115-C

OMM-0084_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288

9. BCM MODBUS AND ADDRESS ASSIGNMENTS

9.1 BCM Modbus Communication & Support Requirements

The Modbus communication support requirements incorporated in the BCM are as follows:

9.1.1 Function Codes

The BCM supports the Modbus Function Codes SHOWN IN

Table 9-1.

Table 9-1: Supported Modbus Function Codes

FUNCTION CODE

DESCRIPTION

03

Read up to 8 contiguous Holding Registers

04

Read up to 8 contiguous Address Registers

06

Write a single 16 bit Register

9.1.2 Modbus Support Requirements

The Modbus Network must conform to the support requirements listed in

Table 9-2.

Table 9-2: Modbus Support Requirements

CHARACTERISTIC

DESCRIPTION

Communication Medium
BMS II/ACS or EMS Master to

BCM Slave


RS485 2-Wire Differential Bus With Shield

RS485 Allowable Cable Length

4000 Feet Maximum

Address Support From Master

EMS

1 to 9 via Address Select Switch (SW1).
(Addresses from 10 to 127 can be implemented via

software)

Transmission Mode Support

RTU (Remote Terminal Unit)

Timing Specifications:
Baud Rate:
Data Framing:
Message Framing:


Character Framing:

Heartbeat Timeout:


Fixed at 9600
8 data bits, no parity, 1 stop bit
Silent period of at least 3.5 character times Before

first character and After last character
No more than 1.5 character times of silence

between received and transmitted characters.

Adjustable (0 or 1 – 240 seconds)