Gf-115-c, Modulex e8 controller and bcm – AERCO Modulex E8 Controls Guide User Manual
Page 23
![background image](/manuals/659381/23/background.png)
PR1: 11/30/12
Page
23 of 112
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
Table 4-2: USER Menu Listing (Continued)
FUNCTION
DESCRIPTION
ENTRY RANGE
DEFAULT
HTG CIRCUIT 1 Sub-Menu
MODE
Displays Timer Mode for Boiler
- - - -, Standby,
Auto 1, Auto 2, Day,
Night
- - - -
T-ROOM DES 1
Not Applicable
T-ROOM DES 2
Not Applicable
T-ROOM DES 3
Not Applicable
T-REDUCED
Not Applicable
T-ABSENCE
Not Applicable
T-LIMIT DAY
Applies during day-time heating periods
- - - -,
-23.0°F–104.0°F
66.0°F
T-LIMIT N
Applies during reduced night-time
periods.
- - - -,
-23.0°F–104.0°F
50.0°F
HEATSLOPE
Indicate number of degrees that the flow
temperature changes if the outside
temperature increases or decreases by
1°F.
0.00 – 3.00
1.20
OPTIM HEAT
Not Applicable
MAX OPT-TIME
Not Applicable
ECONO OPTI
Not Applicable
PC-ENABLE
Not Applicable
RETURN
Press Program Key to exit HTG
CIRCUIT 1 (or 2) sub-menu.
HTG CIRCUIT 2 Sub-Menu
Functions for HTG Circuit 2 are identical to HTG Circuit 1 Functions listed above.
SOLAR M / F Sub-Menu (No Functions Currently In This Sub-Menu)
RETURN
Pressing the Program Key with SOLAR
M/F displayed will change display to
RETURN. Press Program Key again to
redisplay SOLAR M/F. Turning the
Rotary Knob clockwise will advance thd
display to the TIME PROGRAM Menu.