7.5.2 BCM Controller Terminating Resistor and Bias
BCMs can function only as Slave devices on a Modbus Network. Since the Slaves are
connected in a “Daisy-Chain” configuration, the terminating resistor must be enabled only in the
last BCM Controller in the chain. Enabling the terminating resistor is accomplished by
positioning jumper JP1 as shown in
Figure 7-9 only on the BCM Board contained in the last
BCM Controller.
As mentioned in
paragraph 7.5.1, when the controlling Master is an EMS or BAS, pull-down
bias may be implemented by connecting a 1K ohm resistor as shown in
Figure 7-9. DO NOT
install this bias resistor if the controlling Master is an AERCO BMS II or ACS. Bias will be
provided by the BMS II/ACS DIP switches. The last unit in the chain must be energized (even if
disabled) to enable bias.