10.2.3 BMM (Burner Management Module) Fault Codes

The table below lists the fault codes and troubleshooting tips associated with the BMM.

Table 10-4: BMM Fault Codes

CODE DESCRIPTION

EFFECT

CORRECTION

RESET

1

High Limit (STB)

Thermostat

activated

All burners

turned OFF and

Pump ON at

maximum speed.

Check FlowSensor thermal

connection to boiler.

MANUAL - push

reset switch

when

temperature goes

below limit.

2

Low Gas

Pressure

All burners

turned OFF .

Check gas pressure or gas

pressure switch.

AUTOMATIC -

when gas

pressure switch

closes.

4

No flame

detected at

burner start

Burner control

lockout.

Check flame rod or

combustion.

MANUAL - push

reset switch or

cycle power.

5

Flame loss during

run.

Ignition retry.

Check combustion and

wiring.

MANUAL - push

reset switch or

cycle power.

6

High outlet

temperature.

FlowSensor

temperature >

203°F.

All burners

turned OFF and

Pump ON at

maximum speed.

Check Flow Sensor or

system pump

AUTOMATIC -

when

FlowSensor <

176°F.

10

Internal Failure

Ignition is

inhibited.

Contact Factory for new

BCM.

MANUAL - cycle

the power.

11

Flame signal

detected before

ignition.

Ignition is

inhibited.

Disconnect flame rod wire

from BMM. If problem

goes away change flame

rod and/or wire. If problem

does not go away change

BMM.

MANUAL - push

reset switch or

cycle power.

12

FlowSensor fault. All burners

turned OFF.

Check flow sensor or

wiring.

AUTOMATIC

13

Aux Sensor fault

The boiler will

operate from the

FlowSensor

without the

AuxSensor.

Check aux sensor or

wiring.

AUTOMATIC