4-14

T-268-07

Table 4-1. Electrical Control Positions -- BELOW --10_C (+14_F), or --5_C (+23_F) optionally

CONTROL CIRCUIT

COOLING

Holding Zone

**Dehumidification

HEATING

DEFROST

Single-Speed Compressor:
Compressor Contactor

(C)

Energized

De-energized

**

**

De-energized

1

Two-Speed Compressor:
Compressor Contactor

(CH)

Energized

De-energized

**

**

De-energized

1

Compressor Contactor

(CS)

Energized

De-energized

**

**

De-energized

1

Compressor Contactor

(CL)

De-energized

De-energized

**

**

De-energized

1

Condenser Fan

Contactor (CF)

Energized

De-energized

**

**

De-energized

High Speed Evaporator

Contactor (EF)

De-energized

De-energized

Refer to section

3.1.7.a.2

Refer to

section

3.1.7.a.2

De-energized

2

Low Speed Evaporator

Contactor (ES)

Energized

Energized

Refer to section

3.1.7.a.2

Refer to

section

3.1.7.a.2

De-energized

Defrost Relay (TF)

De-energized

De-energized

**

**

Energized

Heater Relay (HR)

De-energized

De-energized

**

**

Energized

INDICATING LIGHTS

Cool

ON

OFF

**

**

OFF

Defrost

OFF

OFF

**

**

ON

In-Range

On -- If In-Range (Refer to paragraph 3.1.4, Code 30)

Heat

OFF

OFF

**

**

ON

POWER CIRCUIT

Compressor

Energized

De-energized

**

**

De-energized

Condenser Fan Motor

Energized

De-energized

**

**

De-energized

Heaters

De-energized

De-energized

**

**

Energized

Evaporator Fan Motors

Energized

Energized

**

**

De-energized

** Dehumidification and heating modes do not operate at set points below --10_C (14_F), or --5_C (23_F) optionally

1

-- May be energized in defrost if snap freeze portion of defrost is run.

2

-- May be energized in defrost if probe check portion of defrost is run.