beautypg.com

Carrier 69NT40-511-199 User Manual

Page 51

background image

SECT

IO

N

3

3-13

T-268-07

CODE

#

DESCRIPTION

TITLE

AL63 Current Over Limit

Alarm 63 is triggered by the current limiting system. If the compressor is ON and

current limiting procedures cannot maintain a current level below the user

selected limit, the current limit alarm is activated.This alarm is a display alarm and

is inactivated by power cycling the unit, changing the current limit via the code

select Cd32, or if the suction modulation valve (SMV) is allowed to open to 100%

and the suction solenoid valve is allowed to open.

AL64

Discharge

Temperature Over

Limit (CPDT)

Alarm 64 is triggered if the discharge temperature is sensed greater than 135_C

(275_F) for three continuous minutes, if it exceeds 149_C (300_F), or if the

sensor is out of range. This is a display alarm and has no associated failure

action.

AL65

Discharge Pressure

Transducer Failure

(DPT)

Alarm 65 is triggered by a compressor discharge transducer reading outside the

valid range of 73.20 cm Hg (30 in Hg) to 32.34 Kg/cm

2

(460 psig). This is a

display alarm and has no associated failure action.

AL66

Suction Pressure

Transducer Failure

(SPT)

Alarm 66 is triggered by a suction pressure transducer reading outside the valid

range of 73.20 cm Hg (30 in Hg) to 32.34 Kg/cm

2

(460 psig). This is a display

alarm and has no associated failure action.

AL67 Humidity Sensor

Failure

Alarm 67 is triggered by a humidity sensor reading outside the valid range of 0%

to 100% relative humidity. If alarm AL67 is active and the dehumidification mode

was previously activated, then the dehumidification mode will be deactivated.

AL68

Condenser Pressure

Transducer Failure

(CPT)

Alarm 68 is triggered by a condenser pressure transducer reading outside the

valid range of 73.20 cm Hg (30 in Hg) to 32.34 Kg/cm

2

(460 psig). This is a

display alarm and has no associated failure action.

AL69

Suction Temperature

Sensor Failure

(CPSS)

Alarm 69 is triggered by a suction temperature sensor reading outside the valid

range of --60_C (--76_F) to 150_C (302_F). This is a display alarm and has no

associated failure action.

NOTE

If the Controller is configured for four probes without a DataCORDER, the DataCORDER alarms AL70

and AL71 (See Table 3-7) will be processed as Controller alarms AL70 and AL71.

The Controller performs self-check routines. if an internal failure occurs, an ERR

#0--5 will appear on the display. This is an indication the Controller needs to be

replaced.

ERROR

DESCRIPTION

#0 -- RAM failure

Indicates that the Controller working memory has

failed.

ERR Internal

Microprocessor

#1 -- Program Memory

failure

Indicates a problem with the Controller program.

ERR

#

Microprocessor

Failure

#2 -- Watchdog time--out

The Controller program has entered a mode whereby

the Controller program has stopped executing.

#3 -- On board timer

failure

The on board timers are no longer operational. Timed

items such as; defrost, etc. may not work.

#4 -- Internal counter

failure

Internal multi-purpose counters have failed. These

counters are used for timers and other items.

#5 -- A-D failure

The Controller’s Analog to Digital (A-D) converter has

failed.

Entr

StPt

Enter Setpoint

(Press Arrow &

Enter)

The Controller is prompting the operator to enter a set point.

LO

Low Mains Voltage

(Function Codes

Cd27--38 disabled

and NO alarm

stored.)

This message will be alternately displayed with the set point whenever the mains

voltage is less than 75% of its proper voltage.

This manual is related to the following products: