3-36

T-268-07

Compressor

Starting Sequence

Is Ambient

Temperature Less

Than 60 ˚F ?

High Speed Start

Has Compressor Run

For 20 Minutes ?

Has Set Point

Been Reached ?

Is The Operating Capacity *

Below Low Speed Capacity ?

Low Speed

Soft Start (See Note B)

Run 20 Minutes

Is Supply 3 ˚F Above Set Point

Or Is Operating Capacity *

Greater Than Low Speed Capacity ?

STEP

A

B

C

D

E

F

G

H

I

YES

YES

YES

YES

YES

Low Speed

Soft Start

(See Note A & B)

Run For 2

Minutes

Are High Speed Switch

Over Conditions Satisfied ?

(Refer To Steps “J & L”)

NO

NO

NO

NO

*

Operating capacity is the required capacity to maintain

container box temperature.

YES

Continue In

Low Speed

NO

Does High Pressure

Switch (HPS) Trip ?

NO

YES

NO

J

Was Ambient Greater

Than 60 ˚F During Start ?

Is Supply Voltage

Greater Than

Required Voltage ** ?

Is Supply Voltage

Greater Than

Required Voltage ** ?

** Required voltage is a function of operating capacity and

supply frequency.

NO

YES

L

YES

NO

NO

NOTE B

Low Speed Soft Start is

performed by closing the
SMV to 0% opening for ten
seconds during the start-up
of the compressor. The SMV
opening is then gradually

increased to the desired value
at the rate of a 3% opening
per second.

NOTE A

During

compressor

operation, if at anytime the
High Pressure Switch (HPS)
trips, the logic will switch to
Low Speed Soft Start.

Continue In

Low Speed

YES

Figure 3-6. Two-Speed Compressor Speed Change Logic -- Perishable Range Only