Carrier 69NT40-511-199 User Manual

Page 58

background image

3-20

T-268-07

CODE

#

DESCRIPTION

TITLE

P4-1

High Speed

Evaporator Fan

Motors Off

Setup: The high speed Evaporator Fan is turned off, a current draw test is done

after 10 seconds.

Pass/Fail Criteria: Passes if change in current draw is within the range

specified. Fails if AL11 or AL12 activates during test.

P5-0 Supply/Return Probe

Test

Setup: The High Speed Evaporator Fan is turned on and run for eight minutes,

with all other outputs de-energized.

Pass/Fail Criteria: A temperature comparison is made between the return and

supply probes.

NOTE: If this test fails, “P5-0” and “FAIL” will be displayed. If both Probe tests

(this test and the PRIMARY/ SECONDARY) pass, the display will read “P5”

“PASS.”

P5-1 Supply Probe Test

Requirements: For units equipped with secondary supply probe only.

Pass/Fail Criteria: The temperature difference between primary and secondary

probe (supply) is compared.

NOTE

If this test fails, “P5-1” and FAIL will be displayed. If both Probe tests (this

and the SUPPLY/ RETURN TEST) pass, because of the multiple tests, the
display will read ’P 5’ ’PASS’.

P5-2 Return Probe Test

Requirements: For units equipped with secondary return probe only.

Pass/Fail Criteria: The temperature difference between primary and secondary

probe (return) is compared.

NOTES

S

If this test fails, “P5-2” and “FAIL” will be displayed. If both Probe

tests (this test and the SUPPLY/ RETURN) pass, because of the
multiple tests, the display will read “P 5,” “PASS.”

S

The results of Pre-Trip tests 5-0, 5-1 and 5-2 will be used to activate or
clear control probe alarms.

Single Speed

C

T

Setup: The compressor is started. If it is the first compressor start, the

compressor reliability enhancement logic (CREL) is executed, running a current

draw test with the additional outputs (if installed) in the following states:

P6-0

g

p

Compressor Test

(For single speed

units)

Component

Normal Logic

(10 seconds)

CREL (3 minutes)

units)

SSV

Closed

Open

SMV

70%

100% (for 3 minutes) then 70%

P-6

Dual Speed

Compressor Tests

(For dual speed

units)

Setup: Prior to this testing the ambient temperature is checked. If the ambient

temperature is less than 60_F, the high speed compressor test will run first. If the

ambient temperature is greater than 60_F, or if the ambient temperature is

invalid, the low speed compressor test will run first. Once the first compressor

test has been completed, the switch over to the other compressor test will follow.

Upon entry to this test section, the high speed evaporator fan should already be

running, if not, it is started. After the evaporator fan has run for five seconds, the

high speed condenser fan is started. After the condenser fan has run for five

seconds, the compressor test is run.