2-12

T-268-07

Orange wire

Power

Red wire

Output

Brown wire

Ground

Input voltage

5 vdc

i. Humidity Sensor

Output voltage

0 to 3.3 vdc

i. Humidity Sensor

(HS) -- Optional

Output voltage readings verses relative humidity (RH) percentage:

(

)

p

30%

0.99 V

50%

1.65 V

70%

2.31 V

90%

2.97 V

2.4 POWER AUTOTRANSFORMER (Optional)

WARNING

Do not attempt to remove power plug(s)
before turning OFF start-stop switch (ST),

unit circuit breaker(s) and external power
source.
Make sure the power plugs are clean and dry

before connecting to any power receptacle.

a. Step-Up Power Autotransformer

The modular transformer (if equipped) is located under

the condenser coil on the left-hand side of the unit (see
Figure 2-9).
The modular transformer (item 1, Figure 2-9) provides
380/460 vac, 3-phase, 50/60 hertz power to the unit

when the 230 vac (black) power cable is connected to a
190/230 vac, 3-phase power source. The module, in
addition to the transformer, includes a 230 vac cable and
a receptacle to accept the unit 460 vac power plug. The
modular transformer may be equipped with an optional

circuit breaker (CB-2).

WARNING

Do not attempt to unplug the power cable
connected to the autotransformer before
performing the following operations: Move
the start-stop switch (ST), the unit circuit
breaker(s), CB-1 and CB-2 (if equipped)

and any external power source to their OFF
positions.

b. To Operate Unit on 190/230 vac Power Supply

1. Make sure that the start-stop switch (ST, on control

panel) and circuit breaker (CB-2 if equipped, on the
modular transformer) are in position “0” (OFF).
Make sure the 460 vac power plug is locked into the

receptacle on the modular transformer and circuit
breaker (CB-1, in the control box) is in position “1”
(ON).

2. Plug the 230 vac (black) cable into a de-energized

190/230 vac, 3-phase power source. Energize the

power source. Set circuit breaker (CB-2 if
equipped) to position “1” (ON). Close and secure
control box door and place the start-stop switch
(ST) in position “1” (ON) to start the unit.

c. To Operate Unit on 380/460 vac Power Supply

1. Make sure start-stop switch (ST, on control panel)

and circuit breaker (CB-1, in the control box) are in
position “0” (OFF).

2. Plug the 460 vac (yellow) cable into a de-energized

380/460 vac, 3-phase power source. Energize the
power source. Place circuit breaker (CB-1) in
position “1” (ON). Close and secure control box

door and then place the start-stop switch (ST) in
position “1” (ON) to start the unit.

1. Dual Voltage Modular Transformer

2. Circuit Breaker (CB-2) 230V (Optional)

3. 460 vac Power Receptacle

2

3

1

Figure 2-9. Power Autotransformer (Optional)