Installation

n

Water System Maintenance

All systems are susceptible to valve and system problems caused

by improper water treatment and system storage procedures.

These guidelines are provided to help avoid valve and water sys-

tem problems resulting from improperly treated water or storage

procedures and to obtain maximum life from the valves.

Durability of valve stems and packings is dependent on maintain-

ing non-damaging water conditions. Inadequate water treatment

or filtration can result in corrosion, scale, and abrasive particle

formation. Scale and particulates can result in stem and packing

scratches and can adversely affect packing life and other parts

of the hydronic system.

To maintain non-damaging conditions, follow these guidelines:
• Clean the system prior to start up.
• Use filtration equipment where needed.
• Properly store off-line systems and monitor water treatment

results.

• Follow the advice of a water treatment professional.

Inspection

Inspect the package and contents for damage. If damaged,

notify the appropriate carrier immediately.
If consultation is necessary, please contact Powers Customer

Service for assistance.

Requirements

• Pipe wrenches
• Flange gaskets, bolts / nuts
• Installer must be a qualified, experienced technician

CAUTION!
• Install the valve with the flow in the direction of the flow

arrows ("A" and "B" ports are inlets and "AB" port is the outlet).

• Do not exceed the ratings of the device.
• Avoid locations where excessive moisture, corrosive fumes, or

vibration are present.

Mounting / Orientation

1. The valve should be mounted in a location that is within the

ambient limits of the actuator. When selecting a location,

allow sufficient room for valve linkage, actuator, and other

accessories and for service of the product.

2. The preferred mounting position for the valve is with the valve

stem vertical above the valve body. Avoid mounting the valve

so that the valve stem is below horizontal.

3. The valves must be piped with two inlets ("A" and "B" ports)

and one outlet ("AB" port).

Flanged Connection

The 596 series flanged valve bodies conform to ANSI Standard

125 Lb. Cast Iron Pipe Flanges. The companion flanges (not

provided) should be the same specification as the valve. The

125 Lb. Flanges have plain flat faces and should not be bolted to

a raised faced flange.
1. All parts should be clean to assure the best results.
2. The pipe with the companion flanges installed should be

properly supported and aligned. Be sure the companion

flange is flush with the face of the valve body flange and lined

up squarely.

3. Use a gasket material (not provided) that is recommended

for the medium being handled. CAUTION! Do not apply pipe

dope to the valve flange, gasket, or companion flange.

4. See Figure-7 for flange and flange bolt details. Figure-8

shows the proper way a flanged valve should be mounted.

Valve

Body

Gasket:

Supplied by Others

Companion

Flange

Figure 8 - Installation of Flanged End Valves

Maintenance

n

Regular maintenance of the total system is recommended to assure sustained performance. See Table-6 for maintenance kit part numbers.

Table - 6 Maintenance Kits for 596MI Valves

Valve Description

Replacement

Replacement

Valve Repair Kit*

Pack Assembly

Gaskets

2.5

596 Pack

596250G

MIGOBMTK

3

596300G

MIHOBMTK

4

596400G

MIJOBMTK

5

596500G

MIKOBMTK

6

596600G

MILOBMTK

* Kit includes replacement packing and stem & plug assembly.