Valve sizing and selection – Powers 596 Series Flowrite II Heavy Duty Control Valves - Type MI Mixing User Manual
Page 3
NOTE: Supply pressures (inlet) are affected by piping sched-
ule, internal surface conditions, and vertical runs (back pres-
sure) so the actual flowing pressure is best measured at the
point of valve use.
Proportional to Mix Supply Flows
Proportional valves when used to blend two water flows con-
trol the output by varying the water temperature to the heat
exchanger at constant flow. These valves require high pres-
sure drops for good control results. They can be sized for a
pressure drop of 20% of the flowing pressure or equal to 25% of
the pressure drop through the heat exchanger at full flow.
Proportional to Bypass Flow
Proportional mixing valves when used to bypass flow are piped
on the outlet side of the hot water source to throttle the water
flow and thereby control heat output. These valves are usually
selected to take a pressure drop up to 50% of the flowing pres-
sure through the valve.
Valve Sizing and Selection
n
3
Table - 1 Water Capacity in Gallons Per Minute
Valve
Cv
Size
Rating
Differential Pressure (∆ in psi)
5
10
15
20
25
30
35
40
45
50
2.5
74
165
234
287
331
370
405
438
468
496
523
3
101
226
319
391
452
505
553
598
638
678
714
4
170
380
538
658
760
850
931
1006
1075
1140
1202
5
290
648
917
1123
1297
1450
1588
1716
1834
1945
2051
6
390
872
1233
1510
1744
1950
2136
2307
2467
2616
2758