TI593UBS

FLOWRITE II TYPE WM TECHNICAL DATA

VALVE
SIZE(in)

AVAILABLE SIZING PRESSURE DIFFERENTIAL –PSI*

Cv1

2

4

6

8

10

15

20

25

30

40

50

1/2

4.2

5.9

8.4

10

12

13

16

19

21

23

27

30

3/4

7.2

10

14

18

20

23

28

33

36

39

46

51

1

12

18

25

30

35

39

48

55

62

68

78

88

1-1/4

20

28

40

49

57

64

78

90

100

110

127

142

1-1/2

26

36

51

62

72

81

99

114

127

140

161

180

2

39

55

79

96

111

124

152

176

197

215

248

278

MAXIMUM WATER CAPACITIES (GALLONS PER MINUTE)

VALVE
SIZE(in)

AVAILABLE SIZING PRESSURE DIFFERENTIAL–PSI

Cv1

2

4

6

8

10

15

20

25

30

40

50

1/2

2.2

3.1

4.4

5.4

6.2

7.0

9.0

10

11

12

14

16

3/4

6.0

8.5

12

15

17

19

23

27

30

33

38

42

1

8.9

13

18

22

25

28

34

40

45

49

56

63

1-1/4

16

22

32

39

45

50

61

71

79

87

100

112

1-1/2

18

25

36

44

51

57

69

80

90

98

113

127

2

30

43

60

74

85

96

117

135

151

165

191

214

* For hot water tempering, use minimum differential of 10 PSI at maximum flow.

MAXIMUM MIXED FLOW–GPM

FLOW THRU BOTTOM PORT (UPPER PORT CLOSED)–GPM

VALVE
SIZE(in)

AVAILABLE SIZING PRESSURE DIFFERENTIAL–PSI

Cv1

2

4

6

8

10

15

20

25

30

40

50

1/2

3.5

4.9

7.0

8.6

9.9

11

14

16

18

19

22

25

3/4

6.0

8.5

12

15

17

19

23

27

30

33

38

42

1

11

16

22

27

32

35

43

50

56

61

71

79

1-1/4

17

24

33

41

47

53

65

75

84

91

106

118

1-/12

24

34

47

58

67

75

92

106

119

130

150

168

2

38

54

76

93

108

120

148

170

191

209

241

269

FLOW THRU UPPER PORT (UPPER PORT CLOSED)–GPM