beautypg.com

Flowrite ii type sd technical data, Maximum water capacities (gallons per minute), Maximum steam capacities (lbs. per hour) – Powers 593 Series Flowrite II Heavy Duty Bronze Globe Control Valves - Heavy Duty Bronze User Manual

Page 4

background image

Page 4

TI593UBS

FLOWRITE II TYPE SD TECHNICAL DATA

Push to Close

VALVE
SIZE
(in)

AVAILABLE PRESSURE DROP FOR SIZING–PSI

Cv1

2

4

6

8

10

15

25

30

40

50

3/4

6

9

12

15

17

19

23

30

33

38

43

1

10

14

20

25

28

32

39

50

54

63

71

1 1/4

16

23

32

40

45

51

62

80

88

101

114

1 1/2

20

29

40

49

57

63

77

100

110

126

142

2

28

54

76

93

107

120

147

190

208

240

269

MAXIMUM WATER CAPACITIES (GALLONS PER MINUTE)

VALVE INLET

PRESSURE–PSIG

SIZE

2

5

10

(in)

AVAILABLE PRESSURE DROP FOR SIZING–PSI

1

2

1

2

3

4

5

2

4

5

8

10

3/4

72 100

78

109

132

150

165

123

170

203

229

250

1

119

166

130

182

219

250

275

204

283

339

382

417

1 1/4

191

266

208

291

351

400

441

327

453

542

611

667

1 1/2

239

333

260

363

439

500

551

409

566

678

764

834

2

454

632

494

690

834

950

1047

777

1075

1288

1452

1584

MAXIMUM STEAM CAPACITIES (LBS. PER HOUR)

VALVE INLET

PRESSURE–PSIG

SIZE

15

25

50

(in)

AVAILABLE PRESSURE DROP FOR SIZING–PSI

MAX

MAX

MAX

6

9

12

15

5

10

15

20

10

20

40

40

3/4

225

268

300

324

243

332

392

433

435

589

688

706

1

376

447

501

540

405

553

653

722

726

982

1147

1177

1 1/4

601

718

801

865

648

885

1044

1156

1161

1572

1835

1884

1 1/2

752

894

1002

1181

810

1106

1305

1445

1451

1965

2293

2355

2

1428

1700

1903

2054

1539

2102

2480

2746

2757

3733

4358

4475