Selecting an Indication Mode
Using function
Pr 0, you can modify the SmartScan default display to show indications for volume, total flow or diameter
sum. Select the required indication mode, as follows:
F
Ind 1: Volume mode: The default screen indicates the volume reading, by means of a value displayed
in the numerical area and the level of the tank graphic.
NOTE: When this mode is selected, you can use Pr 1 or Pr 2 to customize volume measurement
(see the next two
sections in this manual).
F
Ind 2: Totalization for flow mode: The default screen indicates the value for total accumulative flow,
calculated from the point of entering the mode, and updated every 30
seconds.
F
The total amount of flow is shown as a nine-digits value in two
separate screens: high and low. The high digits are indicated by an
H, followed by the first five digits of the value; the low digits are
indicated by an L, followed by the last four digits of the value. You
can toggle between the high and low screens using the NEXT and
BACK buttons (there is no level indication in the tank graphic for this
mode.)
F
In addition, you can toggle between level, distance and flow values
using the same buttons. There are three options available in this
mode that allows you to, either reset the totalization counter, activate
it or deactivate it. Use the NEXT and BACK buttons to toggle
between options, and ENT. to select the desired option:
•
0: Resets the totalization value
•
1: Activates the totalization mode
•
2: Deactivates the totalization mode
Press / Action
Display
Description
Indication Mode Program (Pr 0)
Displays an Indication Option (Ind. 1 or Ind. 2)
or then
Select Indication Option. DO NOT SELECT
(Ind. 3)
Functions
Page
Pr 0 – Selecting an Indication Mode
31
Pr 1 – Manually Inserting Strapping Table Values
32
Pr 2 – Semi-automatic Inserting Strapping Table Values
33
Pr 3 – Entering a Coefficient for Readings
34
Pr 4 – Erasing Strapping Table Values
34
Pr 5 – Configuring Height for a Cone Bottom Tank
35
Pr 6 – Defining the 4-20mA Error Signal (3.7mA or 22mA)
36