Selecting an Indication Mode

Using function

Pr 0, you can modify the SmartScan default display to show indications for volume, total flow or diameter

sum. Select the required indication mode, as follows:

F

Ind 1: Volume mode: The default screen indicates the volume reading, by means of a value displayed

in the numerical area and the level of the tank graphic.


NOTE: When this mode is selected, you can use Pr 1 or Pr 2 to customize volume measurement

(see the next two

sections in this manual).

F

Ind 2: Totalization for flow mode: The default screen indicates the value for total accumulative flow,

calculated from the point of entering the mode, and updated every 30

seconds.

F

The total amount of flow is shown as a nine-digits value in two

separate screens: high and low. The high digits are indicated by an

H, followed by the first five digits of the value; the low digits are

indicated by an L, followed by the last four digits of the value. You

can toggle between the high and low screens using the NEXT and

BACK buttons (there is no level indication in the tank graphic for this

mode.)

F

In addition, you can toggle between level, distance and flow values

using the same buttons. There are three options available in this

mode that allows you to, either reset the totalization counter, activate

it or deactivate it. Use the NEXT and BACK buttons to toggle

between options, and ENT. to select the desired option:

0: Resets the totalization value

1: Activates the totalization mode

2: Deactivates the totalization mode

Press / Action

Display

Description

Indication Mode Program (Pr 0)

Displays an Indication Option (Ind. 1 or Ind. 2)




or then

Select Indication Option. DO NOT SELECT
(Ind. 3)

Functions

Page

Pr 0 – Selecting an Indication Mode

31

Pr 1 – Manually Inserting Strapping Table Values

32

Pr 2 – Semi-automatic Inserting Strapping Table Values

33

Pr 3 – Entering a Coefficient for Readings

34

Pr 4 – Erasing Strapping Table Values

34

Pr 5 – Configuring Height for a Cone Bottom Tank

35

Pr 6 – Defining the 4-20mA Error Signal (3.7mA or 22mA)

36