Setting the 20mA and 4mA Values
SmartSonic enables you to set Distance, Level, Volume or Flow values to be used as 20mA and 4mA settings. The
default value for 20mA is the Tank Height (or the maximum Volume value), and the default value for 4mA is 0 (or the
minimum Volume value).

NOTES: The values for 20 mA and 4 mA must be different, otherwise an Err. 4 message is displayed. Both must also be

less than the tank height value, otherwise an Err. 7

message is displayed.


In both distance and level measurement modes, the dead-zone area affects the maximum values that can be

used for 20 mA/4 mA levels. The maximum 20 mA/4 mA value is tank height minus 0.4 m/1.3 ft.

Press / Action

Display

Description




or and

Move to 20mA (flashing). Press ENT.

Displays the default value, or the previously
entered value.




and

Used to select the desired value. Press ENT
when finished.




then

This puts you in the 4mA Mode. Repeat the
previous two steps. Then press NEXT to go to
Flow Measurements.


Setting the Open Channel Flow Measurements
The PARSH.FLUME function enables you to set flume/weir types and measurements for the SmartSonic. See the section
titled “Open Channel Flow Measurement” later in this manual for further information.

Setting the Tank Height
You can enter the height of your tank using the

TANK h function. The default value is 39.4 feet. If you enter a value that

exceeds this maximum value, an Err. 8

error message is displayed.

Process

Media

Ai

r

Tank

Height

Span

Dead Zone

Tank Height

● Maximum – 39.4ft.


Dead Zone

● Minimum – 1.3ft.


Measurement Range

● Maximum Span –
38.1ft.