90 DeviceNet Objects
Parameter Object
(Class ID 0F
H
)
The Parameter Object provides the interface to the Eccentricity configuration
data. There are 18 Parameter Object instances implemented in the Eccentricity
module.
Instances 1-4 and 7-16 are implemented to provide an alternate method of
setting the configuration parameters with ENGUNIT or EPATH data type.
And Parameter Object instances 17 and 18 provide an alternate method for
setting the Produced Connection Size and Produced Connection Path
attributes for the Poll Connection because these attributes can be difficult to
get/set directly through the Connection Object.
Parameter Object instances 5 and 6 are for setting the update rate of the
eccentricity measurements. The eccentricity update rate is used in place of the
tachometer when no tachometer is available.
Instances
There are 18 instances of this object.
Table C.24 Parameter Object Class Attributes
Attr ID
Access
Rule
Name Data
Type
Description
Semantics
2
Get
Max Instance
UINT
Maximum instance
number of an object in
this class.
Total number of parameter
object instances.
8
Get
Parameter Class
Descriptor
WORD
Bits that describe the
parameter.
Bit 0 Supports Parameter
Instances
Bit 1 Supports Full Attrib.
Bit 2 Must do non-volatile store
Bit 3 Params in non-volatile
9
Get
Config.
Assembly
Instance
UINT
Set to 0
Table C.25 Parameter Object Instances
Instance
Read
Only
Name
Data Type
Valid Values
Default Value
1
No
Transducer 1 Sensitivity Units
USINT
0 = mils
1 = µm
0
2
No
Transducer 2 Sensitivity Units
USINT
0 = mils
1 = µm
0
3
No
Eccentricity Measurement 1
Units
USINT
0 = mils
1 = µm
0
4
No
Eccentricity Measurement 2
Units
USINT
0 = mils
1 = µm
0