Rockwell Automation 1440-VST02-01RA XM-120 Eccentricity Module User Manual
Page 28
Publication GMSI10-UM010C-EN-P - May 2010
20 Installing the XM-120 Eccentricity Module
1
Terminals are internally connected and isolated from the Chassis terminals.
22
Buffer Power 2 IN
Channel 2 buffer power input
Connect to terminal 6 for positive biased transducers or terminal 21 for
negative biased transducers
23
CAN_High
DeviceNet bus connection, high differential (white wire)
24
CAN_Low
DeviceNet bus connection, low differential (blue wire)
25
+24 V Out
Internally connected to 24 V In (terminal 44)
Used to daisy chain power if XM modules are not plugged into each other
26
DNet V (+)
DeviceNet bus power input, positive side (red wire)
27
DNet V (-)
DeviceNet bus power input, negative side (black wire)
28
24 V Common
1
Internally connected to 24 V Common (terminals 43 and 45)
Used to daisy chain power if XM modules are not plugged into each other
If power is not present on terminal 44, there is no power on this terminal
29
4-20 mA 2 (+)
4-20 mA output
300 ohm maximum load
30
4-20 mA 2 (-)
31
Chassis
Connection to DIN rail ground spring or panel mounting hole
32
Chassis
Connection to DIN rail ground spring or panel mounting hole
33
Chassis
Connection to DIN rail ground spring or panel mounting hole
34
Chassis
Connection to DIN rail ground spring or panel mounting hole
35
Chassis
Connection to DIN rail ground spring or panel mounting hole
36
Chassis
Connection to DIN rail ground spring or panel mounting hole
37
Chassis
Connection to DIN rail ground spring or panel mounting hole
38
Chassis
Connection to DIN rail ground spring or panel mounting hole
39
Not Used
40
Switch RTN
Switch return, shared between SetPtMult and Reset Relay
41
Reset Relay
Switch input to reset internal relay (active closed)
42
Reserved
43
24 V Common
1
Internally DC-coupled to circuit ground
44
+24 V In
Connection to primary external +24 V power supply, positive side
45
24 V Common
1
Connection to external +24 V power supply, negative side (internally
DC-coupled to circuit ground)
46
Relay N.C. 1
Relay Normally Closed contact 1
47
Relay Common 1
Relay Common contact 1
48
Relay N.O. 1
Relay Normally Open contact 1
49
Relay N.O. 2
Relay Normally Open contact 2
50
Relay Common 2
Relay Common contact 2
51
Relay N.C. 2
Relay Normally Closed contact 2
Terminal Block Assignments
No.
Name
Description