beautypg.com

Speed measurement parameter, Tachometer parameters, Tachometer transducer parameters – Rockwell Automation 1440-VST02-01RA XM-120 Eccentricity Module User Manual

Page 55

background image

Publication GMSI10-UM010C-EN-P - May 2010

Configuration Parameters 47

Speed Measurement Parameter

Use the speed measurement parameter to configure the filtering performed on
the speed measurement.

Tachometer Parameters

The tachometer parameters define the characteristics of the tachometer and
determine the signal processing that will be performed on the tachometer
signal.

Tachometer Transducer Parameters

Speed Measurement Parameter

Parameter Name

Description

Values/Comments

Exponential Averaging Time
Constant

Sets the 3-dB bandwidth for the digital filter used to
calculate the Speed Value. The 3-dB bandwidth is
roughly equal to 1 / (2

π

x Exponential Averaging

Time Constant). The greater the value entered, the
longer the response of the measured Speed Value to
a change in the input signal (less sensitive to noise
in the signal). See example table below.

Milliseconds

Time Constant
(milliseconds)

-3dB Frequency

(Hz)

Settling Time

(milliseconds)

5

31.8310

11

10

15.9155

22

20

7.9577

44

50

3.1831

110

100

1.5915

220

1200

0.1326

2640

Tachometer Transducer Parameters

Parameter Name

Description

Values/Comments

Tachometer Name (XM Serial
Configuration Utility only)

A descriptive name to help identify the tachometer in
the XM Serial Configuration Utility software.

Maximum 18 characters

Fault Low

The minimum, or most negative, expected DC
voltage from the transducer.

Volts

Note: A voltage reading outside this
range constitutes a transducer fault.

Fault High

The maximum expected DC voltage from the
transducer.

Transducer 3 Status (EDS File
only)

States whether a transducer fault condition exists on
the tachometer channel. If a fault exists, the speed
value may not be accurate.

Possible status values: No Fault

Fault