Basic operations, Powering up the module, Manually resetting relays – Rockwell Automation 1440-VST02-01RA XM-120 Eccentricity Module User Manual
Page 47: Powering up the module manually resetting relays
Publication GMSI10-UM010C-EN-P - May 2010
Installing the XM-120 Eccentricity Module 39
Relay Indicator
Basic Operations
Powering Up the Module
The module performs a self-test at power-up. The self-test includes an LED
test and a device test. During the LED test, the indicators will be turned on
independently and in sequence for approximately 0.25 seconds.
The device test occurs after the LED test. The Module Status (MS) indicator is
used to indicate the status of the device self-test.
Refer to Module Indicators on page 37 for more information about the LED
indicators.
Manually Resetting Relays
The XM-120 has an external reset switch located on top of the module, as
shown in Figure 2.24.
Color
State
Description
Red
Off
On-board relay is not activated.
Solid
On-board relay is activated.
MS Indicator State
Description
Flashing Red and Green
Device self-test is in progress.
Solid Green or Flashing Green
Device self-test completed successfully,
and the firmware is valid and running.
Flashing Red
Device self-test completed, the hardware is
OK, but the firmware is invalid. Or, the
firmware download is in progress.
Solid Red
Unrecoverable fault, hardware failure, or
Boot Loader program may be corrupted.