Transducer object (class id 328h), Class attributes, Instances – Rockwell Automation 1440-VST02-01RA XM-120 Eccentricity Module User Manual
Page 113: Instance attributes, Class attributes instances instance attributes, Transducer object (class id 328

Publication GMSI10-UM010C-EN-P - May 2010
DeviceNet Objects 105
Transducer Object
(Class ID 328
H
)
The Transducer Object models a transducer.
Class Attributes
The Transducer Object provides no class attributes.
Instances
There are 3 instances of this object. Transducer Object instance 1 is for
Eccentricity Channel 1. Transducer Object instance 2 is for Eccentricity
Channel 2. And Transducer Object instance 3 is for the tachometer channel.
Instance Attributes
Table C.46 Transducer Object Instance Attributes
Attr ID
Access
Rule
Name Data
Type
Description
Semantics
3
Get
DC Bias
REAL
The measured average DC
bias of the transducer
signal in volts.
Volts
4
Get
Status
BOOL
Indicates whether a
transducer fault exists
(the measured DC Bias is
outside the range
specified by Fault High
and Low).
0 = No fault
1 = A transducer fault exists
5
Get/Set
Sensitivity
Value
REAL
Value of the sensitivity of
the transducer in
millivolts per Sensitivity
Units.
6
Get/Set
Sensitivity Units ENGUNIT
Units of the denominator
of the Sensitivity Value.
See DeviceNet Specification
Volume 1 Appendix K. Also see
Parameter Object instances 1
and 2.
Valid values:
mils = 0800 hex
µm = 2203 hex
7
Get/Set
Fault High
REAL
The maximum expected
DC Bias voltage from the
transducer in volts.
Volts