Instances, Instance attributes, Instances instance attributes – Rockwell Automation 1440-VST02-01RA XM-120 Eccentricity Module User Manual
Page 106
Publication GMSI10-UM010C-EN-P - May 2010
98 DeviceNet Objects
Instances
There are 5 instances of this object.
Instance Attributes
Table C.35 Relay Object Instance Attributes
Attr ID
Access
Rule
Name Data
Type
Description
Semantics
3
Get
Relay Status
BOOL
The current status of the
relay.
0 = Off
1 = On
4
Get/Set
Relay Enable
BOOL
Indicates whether this
relay object is enabled.
0 = Disabled
1 = Enabled
5
Get/Set
Latch Enable
BOOL
Indicates whether this
relay latches (requires a
reset command to
deactivate).
0 = Nonlatching
1 = Latching
6
Get/Set
Failsafe Enable
BOOL
Indicates whether this
relay is normally
energized (activated
during power loss).
0 = Non-failsafe (not normally
energized)
1 = Failsafe (normally energized)
7
Get/Set
Delay
USINT
The time period that the
voting logic must be true
before the relay is
activated.
0 to 25.5 seconds
(specified in tenths of seconds)
8
Get/Set
Name
STRING2
A name to help identify
the relay.
18 characters maximum
9
Get/Set
Alarm Level
BYTE
Specifies what alarm
status values will cause
the relay to activate.
0 = Normal
1 = Alert
2 = Danger
3 = Disarm
4 = Xdcr Fault
5 = Module Fault
6 = Tachometer Fault
10
Get/Set
Alarm Identifier
A
EPATH
Identifies the first alarm
status the relay monitors.
See Parameter Object instances
7 to 11.