Class attributes, Spectrum waveform measurement object (class id 324, Services – Rockwell Automation 1440-VST02-01RA XM-120 Eccentricity Module User Manual
Page 107
Publication GMSI10-UM010C-EN-P - May 2010
DeviceNet Objects 99
Services
1
Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.
Spectrum Waveform
Measurement Object
(Class ID 324
H
)
The Spectrum/Waveform Measurement Object models a spectrum and
waveform measurement. The Eccentricity module implements only the
waveform measurement and not the spectrum measurement.
Class Attributes
The Spectrum/Waveform Measurement Object provides no class attributes.
11
Get/Set
Alarm Identifier
B
EPATH
Identifies the second
alarm status the relay
monitors.
See Parameter Object instances
12 to 16.
12
Get/Set
Logic
USINT
Indicates the number of
associated alarms that
must have a status value
specified by Alarm Level
in order to activate the
relay.
0 = Ignore Alarm Identifier B
and activate the relay based on
the status of Alarm Identifier
A.
1 = Activate the relay if the
status of either Alarm
Identifier A or B matches any
of the statuses specified by
Alarm Level.
2 = Activate the relay if the
status of both Alarm Identifier
A and B match any of the
statuses specified by Alarm
Level.
14
Get
Relay Installed
BOOL
Indicates whether an
actual relay is associated
with this instance.
0 = Not installed
1 = Installed
Table C.35 Relay Object Instance Attributes
Attr ID
Access
Rule
Name Data
Type
Description
Semantics
Table C.36 Relay Object Services
Service
Code
Class/Instance Usage
Name
Description
05
h
Class/Instance
Reset
Resets latched relay(s).
0E
h
Class/Instance
Get_Attribute_Single
Returns a single attribute.
10
h
Class/Instance
Set_Attribute_Single
Sets a single attribute.
1