Monitor data parameters – Rockwell Automation 1440-VST02-01RA XM-120 Eccentricity Module User Manual
Page 66

Publication GMSI10-UM010C-EN-P - May 2010
58 Configuration Parameters
Monitor Data Parameters
Monitor Data Parameters
Parameter Name
Description
Values/Comments
Channel Status (XM Serial
Configuration Utility only)
States whether a fault condition exists on the
associated channel. If a fault exists, the eccentricity
measurement may not be accurate.
The following conditions can cause a fault:
•
a transducer fault on the associated channel
•
no tachometer signal or a transducer fault exists
on the tachometer channel
•
the module is in Program mode
Possible status values: No Fault
Fault
Eccentricity
Shows the measured eccentricity value.
These values get updated after:
•
the number of Pulses per
Revolution has occurred, or
•
the Eccentricity Update Rate has
elapsed
Maximum Gap
The maximum measured transducer gap value.
Minimum Gap
The minimum measured transducer gap value.
Gap Value
Shows the measured transducer gap value. This
value is compared with Fault High and Fault Low
to determine whether the transducer is working
properly.
Speed Status (XM Serial
Configuration Utility only)
States whether a fault condition (no tachometer
signal or transducer fault) exists on the tachometer
channel. If a fault exists, the speed and DC Bias
values may not be accurate.
Possible status values: No Fault
Fault
Shows the measured average DC offset of the
tachometer signal. This value is compared with
Fault High and Fault Low to determine whether
the tachometer is working properly.
Speed Value
Shows the measured speed value.
XM Configuration
Utility
EDS File
Xdcr DC Bias
Transducer 3
Measured
DC Bias