Publication GMSI10-UM010C-EN-P - May 2010

Configuration Parameters 45

Measurement Parameters

Eccentricity Measurement Parameters

Use these parameters to configure the engineering units and update rate for
the eccentricity measurements. There are two instances of the eccentricity
measurement parameters, one for each channel.

Waveform Parameters

There are two instances of the waveform parameters, one for each channel.
Use these parameters to set up the waveform measurements.

TIP

The Eccentricity Update Rate parameter is for
installations where the tachometer signal is not available.

Eccentricity Measurement Parameters

Parameter Name

Description

Values/Comments

Eccentricity Units

The data units of the measured values.

Options: mils

µm

Eccentricity Update Rate

The update rate for the eccentricity, min gap, and
max gap measurements.

Enter a value from 1 to 255 seconds.

Note: This value is used when the
tachometer is disabled (Pulses Per
Revolution
set to zero) or a fault
condition exists on the tachometer
channel.

Waveform Parameters

Parameter Name

Description

Values/Comments

Waveform Period

The total period of the waveform measurement.

Seconds

Number of Points

The number of samples in the waveform
measurement.

Options: 256

512
1024
2048