PowerFlex 700S and 700H Frames 10...14 IP00, NEMA/UL Open Power Structures
Table 13 - 480V AC Input Protection Devices
Drive
Catalog
Number
Fram
e
HP Rating
Input
Ratings
Dual Element Time Delay Fuse Non-Time Delay Fuse
Bussmann Style Semi-
Conductor Fuse
Circuit
Breaker
(5)
Motor Circuit
Protector
(7)
ND
HD
Amps
Min.
(2)
Max.
(3)
Min.
(2)
Max.
(3)
Max.
(6)
Max.
20xD385
10
300
-
372
500
850
500
1100
170M5813
1100
600
-
250
302
400
650
400
900
170M5813
900
400
20xD460
10
350
-
444
600
1000
600
1300
170M8547
1300
600
-
300
388
500
850
500
1100
170M8547
1100
600
20xD500
10
450
-
483
650
1000
650
1500
170M8547
1500
700
-
350
423
550
900
550
1200
170M8547
1200
600
20xD590
11
500
-
570
750 (1 per phs)
375 (2 per phs)
1300
750 (1 per phs)
375 (2 per phs)
1700
170M5813
1700
800
-
450
524
700 (1 per phs)
350 (2 per phs)
1100
700 (1 per phs)
350 (2 per phs)
1500
170M5813
1500
700
20xD650
11
500
-
628
800 (1 per phs)
400 (2 per phs)
1400
800 (1 per phs)
400 (2 per phs)
1900
170M5813
1900
800
-
500
594
750 (1 per phs)
375 (2 per phs)
1300
750 (1 per phs)
375 (2 per phs)
1700
170M5813
1700
800
20xD730
11
600
-
705
900 (1 per phs)
450 (2 per phs)
1600
900 (1 per phs)
450 (2 per phs)
2100
170M5813
2100
900
-
500
655
850 (1 per phs)
425 (2 per phs)
1400
850 (1 per phs)
425 (2 per phs)
1900
170M5813
1900
900
20xD820
12
700
-
792
1000 (1 per phs)
500 (2 per phs)
1800
1000 (1 per phs)
500 (2 per phs)
2400
170M8547
2400
1000
-
600
735
900 (1 per phs)
475 (2 per phs)
1600
900 (1 per phs)
475 (2 per phs)
2100
170M8547
2100
1000
20xD920
12
800
-
888
1200 (1 per phs)
600 (2 per phs)
2000
1200 (1 per phs)
600 (2 per phs)
2700
170M8547
2700
1200
-
700
826
1100 (1 per phs)
550 (2 per phs)
1800
1100 (1 per phs)
550 (2 per phs)
2400
170M8547
2400
1200
20xD1K0
12
900
-
994
1300 (1 per phs)
650 (2 per phs)
2300
1300 (1 per phs)
650 (2 per phs)
3000
170M8547
3000
1300
-
800
927
1200 (1 per phs)
600 (2 per phs)
2000
1200 (1 per phs)
600 (2 per phs)
2700
170M8547
2700
1200
20xD1K1
13
1000
-
1110
1400 (1 per phs)
700 (2 per phs)
2500
1400 (1 per phs)
700 (2 per phs)
3400
170M6466
(4)
3400
1400
-
900
994
1300 (1 per phs)
650 (2 per phs)
2300
1300 (1 per phs)
650 (2 per phs)
3000
170M6466
(4)
3000
1300
20xD1K3
13
1200
-
1255
1600 (1 per phs)
800 (2 per phs)
2900
1600 (1 per phs)
800 (2 per phs)
3900
170M6466
(4)
3900
1600
-
1000
1110
1400 (1 per phs)
700 (2 per phs)
2500
1400 (1 per phs)
700 (2 per phs)
3400
170M6466
(4)
3400
1400
20xD1K4
13
1250
-
1400
1800 (1 per phs)
900 (2 per phs)
3200
1800 (1 per phs)
900 (2 per phs)
4300
170M6466
(4)
4300
1800
-
1000
1158
1500 (1 per phs)
750 (2 per phs)
2700
1500 (1 per phs)
750 (2 per phs)
3600
170M6466
(4)
3600
1500
20xD1K7
(1)
14
1500
-
1709
2200 (1 per phs)
750 (3 per phs)
3800
2200 (1 per phs)
750 (3 per phs)
5300
170M6466
5300
2200
-
1400
1545
2000 (1 per phs)
675 (3 per phs)
3600
2000 (1 per phs)
675 (3 per phs)
4800
170M6466
4800
2000
20xD2K1
(1)
14
1900
-
2076
2600 (1 per phs)
900 (3 per phs)
4800
2600 (1 per phs)
900 (3 per phs)
6400
170M6466
6400
2600
-
1700
1873
2400 (1 per phs)
800 (3 per phs)
4300
2400 (1 per phs)
800 (3 per phs)
5800
170M6466
5800
2400
20xD2K7
(1)
14
2300
-
2607
3000 (1 per phs)
1100 (3 per phs)
6000
3000 (1 per phs)
1100 (3 per phs)
8000
170M6466
8000
3300
-
2000
2220
2800 (1 per phs)
900 (3 per phs)
5000
2800 (1 per phs)
900 (3 per phs)
6900
170M6466
6900
2800
(1) Not available with 700S Control.
(2) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(3) Maximum protection device size is the highest rated device that supplies drive protection.
(4) These fuses and disconnect are supplied with AC input NEMA/UL Type 1 drives.
(5) Inverse time breaker. Ratings shown are maximum.
(6) Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(7) Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not
to exceed 1300% FLA.