Troubleshooting

Problem

Possible

Causes

Suggested

Solutions

Line fuse blows

1. Line fuses are the
wrong size.

2. Motor cable or
armature is shorted
to ground.

3. Nuisance tripping
caused by a
combination of
ambient conditions
and high-current
spikes
(i.e. reversing).

4. Field circuit is
open.

1. Check that line
fuses are properly
sized.

2. Check motor cable
and armature for
shorts.

3. Add a blower to
cool the drive
components;
decrease FWD TQ
and REV TQ settings;
check wiring to be
sure noise is reduced
or eliminated.

4. Send in drive to
Reliance Electric
repair department.