DWELL TIME

The DWELL TIME trimpot setting determines the length
of time the motor stops before rotating in the opposite
direction. DWELL TIME only works when the drive is set
for Mode 2 and Mode 3 (see page 24 for limit switch
operating modes).

There are 10 DWELL TIME settings (0 thru 9). Set the
DWELL TIME to 0 (the factory setting) for 0.1 second
delay. Increasing the setting one increment higher adds 0.1
second to the dwell time. Set the DWELL TIME trimpot to
9 for approximately 1 second delay.