Alarm and Relay Status Parameters

Alarm and Relay Status Parameters

Parameter Name

Description

Values/Comments

Alarm Status

States the current status of the alarm.

Possible status values:

Normal - The alarm is enabled, the
device is in Run mode, there is no
transducer fault, and the current
measurement is not within the Alert
or Danger Threshold value(s).

Alert - The alarm is enabled, the
device is in Run mode, there is no
transducer fault, and the current
measurement is in excess of the
Alert Threshold value(s) but not in
excess of the Danger Threshold
value(s).

Danger - The alarm is enabled, the
device is in Run mode, there is no
transducer fault, and the current
measurement is in excess of the
Danger Threshold value(s).

Disarm-The alarm is disabled or the
device is in Program mode.

Transducer Fault - The alarm is
enabled, the device is in Run mode,
and a transducer’s DC bias is outside
the transducer’s Fault High/Fault
Low
range.

Tachometer Fault - The alarm is
enabled, the device is in Run mode,
a tachometer fault exists, but there
is no transducer fault.

Module Fault - Hardware or
firmware failure, or an error has
been detected and is preventing
proper operation of the device.

Relay Status

States the current status of the relay.

Possible status values: Activated

Not Activated