beautypg.com

Module status (ms) indicator, Network status (ns) indicator – Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual

Page 54

background image

Publication GMSI10-UM003D-EN-P - May 2010

46

Figure 2.33 LED Indicators

The following tables describe the states of the LED status indicators.

Module Status (MS) Indicator

1

Program Mode - Typically this occurs when the module configuration settings are being updated with the XM
Serial Configuration Utility. In Program Mode, the module does not perform its normal functions. The signal
processing/measurement process is stopped, and the status of the alarms is set to the disarm state to prevent
a false alert or danger status.

2

Run Mode - In Run Mode, the module collects measurement data and monitors each vibration measurement
device.

Network Status (NS) Indicator

AERODERIVATIVE

1440-VAD02-01RA

Module Indicators

Color

State

Description

No color

Off

No power applied to the module.

Green

Flashing Red

Module performing power-up self test.

Flashing

Module operating in Program Mode

1

.

Solid

Module operating in Run Mode

2

.

Red

Flashing

Application firmware is invalid or not loaded.
Download firmware to the module.

Firmware download is currently in progress.

Solid

An unrecoverable fault has occurred. The module may
need to be repaired or replaced.

Color

State

Description

No color

Off

Module is not online.

Module is autobauding.

No power applied to the module, look at Module
Status LED.

Green

Flashing

Module is online (DeviceNet) but no connections are
currently established.

1

Solid

Module is online with connections currently
established.