Vector measurement object (class id 329h), Class attributes, Instances – Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual
Page 147: Instance attributes, Class attributes instances instance attributes, Vector measurement object (class id 329
Publication GMSI10-UM003D-EN-P - May 2010
139
Vector Measurement
Object
(Class ID 329
H
)
The Vector Measurement Object models the measurement of the amplitude
and phase of the input signal at a specific multiple of the machine speed.
Class Attributes
The Vector Measurement Object provides no class attributes.
Instances
There are 2 instances of this object.
Instance Attributes
Table C.50 Vector Measurement Object Instances
Instance
Description
1
Channel 1 Tracking Measurement
2
Channel 2 Tracking Measurement
Table C.51 Vector Measurement Object Instance Attributes
Attr ID
Access
Rule
Name Data
Type
Description
Semantics
3
Get
Magnitude
Value
REAL
The measured magnitude
value.
4
Get
Phase Value
REAL
The measured phase
value.
Degrees
5
Get
Status
BOOL
Indicates if a fault or
alarm has occurred.
0 = Operating without alarms of
faults.
1 = Alarm or fault condition
exists. The Value attributes
may not represent the actual
field value.
6
Get
Magnitude Data
Units
ENGUNIT
The units context of the
Magnitude Value
attribute.
This setting is determined by the
Channel Object’s Output Data
Units setting (see page 125).
7
Get/Set
Speed Value
REAL
The speed at which the
magnitude and phase are
measured.
A multiple of the measured
machine speed
0.1
≥
speed multiple
≤
20
8
Get
Speed Data
Units
ENGUNIT
The units context of the
Speed Value attribute.
See DeviceNet Specification
Volume 1 Appendix K.
This is set to Orders (0x0B00).