Alarm parameters – Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual
Page 68
Publication GMSI10-UM003D-EN-P - May 2010
60
Alarm Parameters
The Alarm parameters control the operation of the alarms (alert and danger
level) and provide alarm status. The XM-123 provides 12 alarms. The alarms
are not restricted to a channel. Use the parameters to configure which
measurement the alarm is associated with, as well as the behavior of the alarm.
Trigger Threshold
The signal level to be used as the trigger value when
in Manual Trigger mode.
Enter a value from +16 to -16 volts dc.
Note: This value is not used in Auto
Trigger mode.
Trigger Slope
The input signal slope to be used as the trigger value
when in Manual Trigger mode.
Options: Positive
Negative
Note: This value is not used in Auto
Trigger mode.
Tachometer Signal Processing Parameters
Parameter Name
Description
Values/Comments
Alarm Parameters
Parameter Name
Description
Values/Comments
Number (1-12) (XM Serial
Configuration Utility only)
Sets the alarm to be configured in the XM Serial
Configuration Utility. There are 12 alarms in the
XM-123. The alarms are not restricted to a channel.
Select a number from 1 to 12.
Name (XM Serial Configuration
Utility only)
A descriptive name to identify the alarm in the XM
Serial Configuration Utility.
Maximum 18 characters
Enable
Enable/disable the selected alarm.
Note: The Alarm Status is set to "Disarm" when the
alarm is disabled.
XM Configuration
Utility
EDS File
Check to Enable
Enabled
Clear to Disable
Disabled