Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual
Page 30

Publication GMSI10-UM003D-EN-P - May 2010
22
Table 2.1 shows the on-board relay connections for the XM-123.
Figures 2.9 and 2.10 illustrate the behavior of the NC and NO terminals when
the relay is wired for failsafe, alarm or nonalarm condition or non-failsafe,
alarm or nonalarm condition.
IMPORTANT
All XM relays are double pole. This means that each relay
has two contacts in which each contact operates
independently but identically. The following information
and illustrations show wiring solutions for both contacts;
although, in many applications it may be necessary to wire
only one contact.
TIP
The Expansion Relay module may be connected to the
module to provide additional relays. Refer the XM-441
Expansion Relay Module User Guide for wiring details.
IMPORTANT
The NC/NO terminal descriptions (page 20) correspond
to a de-energized (unpowered) relay.
When the relay is configured for non-failsafe operation, the
relay is normally de-energized.
When the relay is configured for failsafe operation, the
relay is normally energized, and the behavior of the NC and
NO terminals is inverted.
Table 2.1 Relay Connections for XM-123
Configured for
Failsafe Operation
Relay 1 Terminals
Nonalarm
Alarm
Wire Contacts
Contact 1
Contact 2
Closed Opened
COM
47
50
NO
48
49
Opened
Closed
COM 47
50
NC
46
51
Configured for
Non-failsafe Operation
Relay 1 Terminals
Nonalarm
Alarm
Wire Contacts
Contact 1
Contact 2
Closed
Opened
COM
47
50
NC
46
51
Opened
Closed
COM
47
50
NO
48
49