Channel Signal Processing
Parameters
The channel signal processing parameters determine the signal processing that
will be performed on the input signals. Use these parameters to select the
output data units and the low cutoff frequency for each channel. There are two
instances of the signal processing parameters, one for each channel.
Full Scale
The maximum signal level expected to be processed
by the channel. This value is used to determine the
programmable gain settings across each stage of the
channel’s analog signal processing circuit.
Volt
Important: See Appendix D for further
guidance and recommended Full Scale
value settings.
Auto Full Scale (XM Serial
Configuration Utility only)
Calculates a new Full Scale value based upon the
current input signal level.
Enter a safety factor value greater
than or equal to 1.0.
The safety factor is a number that will
be multiplied to the current signal
level to determine the new Full Scale
setting.
Channel Transducer Parameters
Parameter Name
Description
Values/Comments
Channel Signal Processing Parameters
Parameter Name
Description
Values/Comments
Output Data Unit
The data units of the measured values.
The available options depend on the
Eng. Units selection. See page
51.
Very Low HPF Frequency (EDS
File only)
Shows the corner frequency for the Very Low high
pass filter option.
Eng. Units
Output Data
Unit Options
g
g
ips
mm/sec
ips or mm/sec
ips
mil
mm/sec
um
mils or um
mils
um
Volt
volt
Pa or psi
Pa
psi