4-20 mA Output Parameters

The 4-20 mA output parameters define the characteristics of the two 4-20 mA
output signals. The parameters are the same for each output.

4-20 mA Parameters

Parameter Name

Description

Options/Comments

Enable

Enables/disables the 4-20 mA output.

Measurement

Sets the type of measurement and the channel that
the 4-20 mA output signal will track.

Options: Ch1 / Ch2 Overall

Ch1 / Ch2 Tracking
Magnitude *
Ch1 / Ch2 Band *
Speed
Ch1 / Ch 2 DC Bias

Important: The tracking and band
measurement selections depend on
which filter measurement (Bandpass
Filter
or Tracking Filter) is selected.
See Aeroderivative Measurement
Parameter on page 55.

For example in the XM Serial
Configuration Utility, if you selected
Bandpass Filter for channel 1 and
Tracking Filter for channel 2, then
the measurement selection would
include "Ch1 Band" and "Ch2 Tracking
Magnitude" but not "Ch2 Band" or
"Ch1 Tracking Magnitude."

Min Range

The measured value associated with the 4 mA.

Same measurement unit as Output
Data Unit
selection for the specified
channel.

Max Range

The measured value associated with the 20 mA.

XM Configuration
Utility

EDS File

Check to enable

Enabled

Clear to disable

Disabled

IMPORTANT

Measured values between Min Range and Max Range are
scaled into the range from 4.0 to 20.0 to produce the
output value. The Min Range value does not have to be
less than the Max Range value. If the Min Range value is
greater than the Max Range value, then the output signal
is effectively inverted from the input signal.