Services, Band measurement object (class id 31eh), Class attributes – Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual
Page 130: Band measurement object (class id 31e
Publication GMSI10-UM003D-EN-P - May 2010
122
Services
1
Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.
Band Measurement Object
(Class ID 31E
H
)
The Band Measurement Object models the measurement of the amplitude of a
signal within a narrow frequency range.
Class Attributes
The Band Measurement Object provides no class attributes.
17
Get/Set
Speed Range
Low
REAL
Indicates the lesser
threshold of the machine
speed range for which the
alarm is enabled (disabled
at lesser speeds).
CPM
(Must be less than Speed
Range High)
18
Get/Set
Name
STRING2
A name to help identify
this alarm.
19
Get/Set
Measurement
Identifier
EPATH
Identifies the
measurement object to
which this alarm is
applied.
See Parameter Object instances
7 to 18.
20
Get/Set
Inhibit Tach
Fault
BOOL
Determines whether the
Tach Fault status is
prohibited during the
startup period.
0 = Tach Fault allowed
1 = Tach Fault inhibited
Table C.28 Alarm Object Instance Attributes
Attr ID
Access
Rule
Name Data
Type
Description
Semantics
Table C.29 Alarm Object Services
Service
Code
Class/Instance Usage
Name
Description
0E
h
Instance
Get_Attribute_Single
Returns a single attribute.
10
h
Instance
Set_Attribute_Single
Sets a single attribute.
1