Rockwell Automation WebPak 3000 DC Drives Hardware Reference, Installation and Troubleshooting User Manual
Page 50

4-8
WebPak 3000 DC Drive Hardware Reference
Table 4.2 - Alarm Codes
CODE
DISPLAY
DESCRIPTION
A00002
AC LINE VOLTAGE
LOW
The AC line voltage fell below 90% of
NOMINAL AC LINE VOLTS (P.307)
.
Possible causes:
•
Low AC line voltage.
•
Incorrect value entered for
NOMINAL AC LINE VOLTS (P.307).
•
Blown AC line fuse(s).
A00003
AC LINE VOLTAGE
HIGH
The AC line voltage rose above 115% of
NOMINAL AC LINE VOLTS
(P.307)
Possible causes:
•
High AC line voltage.
•
Incorrect value entered for
NOMINAL AC LINE VOLTS (P.307).
A00004
NETWORK
COMMUNICATION
TIMEOUT
Network Communications is missing or failed to communicate with
master. (
CONTROL SOURCE SELECT
set to
NETWORK
)
Possible causes:
•
NETW CONNECT TYPE
(P.910) was changed from
BASIC
to
FULL
.
•
NETW DROP NUMBER
(P.900) was changed.
•
Network Option cable connections are loose or not connected.
•
Network Option device failed or master communications failed.
A00005
INVERTING FAULT
AVOIDED
The inverting fault
avoidance logic has detected conditions that could
have caused an inverting fault. The drive took action to avoid an actual
inverting fault.
A00030
1)
MAIN CONTACTOR
DID NOT OPEN
The main contactor (K1M) did not open following a stop.
Possible causes:
•
Disconnected, loosely connected, or damaged main contactor (K1M)
or Aux. contactor (K1) wiring.
•
Main contactor or Aux. Main contactor failure.
•
Disconnected, loosely connected, or damaged main contactor control
wiring (MCR).
A00031
2)
MAIN CONTACTOR
DID NOT CLOSE
The main contactor (K1M) did not close following a run or jog
command.
Possible causes:
•
Disconnected, loosely connected, or damaged main contactor (K1M)
or Aux. contactor (K1) wiring.
•
Main contactor or Aux. Main contactor failure.
•
Disconnected, loosely connected, or damaged main contactor control
wiring (MCR).
1) When after stop command, the auxiliary contactor does not indicate that the main contactor opened,
this alarm indication is 1000 msec
time delayed.
2) When after start command, the auxiliary contactor does not indicate that the main contactor closed,
this alarm indication is 1000 msec time delayed.