background image

4-2

WebPak 3000 DC Drive Hardware Reference

4.4

Verifying Optional Kits

Verify that each optional kit has been installed correctly according the appropriate instructions.
Refer to the appropriate instruction manuals. See section 1.5 and 1.6.

4.5

Checking the Regulator Led Status

Two LEDs are located on the Regulator board to indicate the operating status of the Regulator
board. The cover on the OIM must be removed to observe these LEDs. Check and observe
these LEDs when the OIM is not communicating with the regulator. Typically, there will be no
fault indication on the display when the OIM is not communicating with the regulator board.
If a fault can be displayed, the fault would be OIM COMMUNICATIONS TIMEOUT (F00011).

The two LEDs are labeled

CPU OK

and

OIM COMM OK. CPU OK

will be on whenever the inputs

and outputs are being scanned (I/O is not scanned during power-up diagnostics and following
certain faults).

OIM COMM OK

will be on whenever the regulator board and the OIM are commu-

nicating properly. The following table summarizes the possible states of the two LED indicators.

CPU OK LED

OIM COMM OK LED

Indication(s) and Action(s)

Off

Off

No power - verify that the drive power is on. Check for 24 volt at

the regulator board terminals 1 and 15 (COM).

LED failure - cycle power and verify that both LED's illuminate

briefly (lamp test).

Power-up diagnostics failed - replace the Regulator board.

On

Combination not used.

Blink

Combination not used.

On

Off

I/O is being scanned, regulator is not communicating with the

OIM - check OIM cable, check voltages at the OIM.

On

I/O is being scanned, the regulator is communicating with the

OIM, no faults - this is a normal condition, no action is required.

I/O is being scanned, the regulator is communicating with the

OIM, - diagnose/correct the fault condition and reset the fault
from the selected control source fault reset.

Power-up diagnostics in progress (lamp test).

Blink

Combination not used.

Blink

Off

I/O is not being scanned, Regulator board is not communicating

with the OIM,
- initialize card: set P.010, P.306, P.307 and
execute MEMORY SAVE,
- press the OIM fault reset key
- check the OIM cable or cycle power.

On

I/O is not being scanned, the regulator board is communicating

with the OIM,
- initialize card: set P.010, P.306, P.307 and
execute MEMORY SAVE,
- press OIM fault reset key,- record information on the fault.

Blink

I/O is not being scanned, regulator board is not communicating

with the OIM,
- initialize card: set P.010, P.306, P.307 and execute M. S.
- press the OIM fault reset key
- record any information about the fault and cycle power.