beautypg.com

Rockwell Automation WebPak 3000  DC Drives Hardware Reference, Installation and Troubleshooting User Manual

Page 47

background image

Troubleshooting/Diagnostics

4-5

Table 4.1 - Fault Codes (Continued)

CODE

DISPLAY

DESCRIPTION

F00012

ARMATURE OVER
VOLTAGE

Armature voltage exceeded 130% of

MOTOR RATED ARM VOLTS (P.009)

.

Possible causes:

MOTOR RATED ARM VOLTS

not set properly.

Improper voltage loop tuning.

F00013 NETWORK

COMMUNICATION
TIMEOUT

Network Communications is missing or failed to communicate with
master. (

CONTROL SOURCE SELECT

set to

NETWORK

)

Possible causes:

NETW CONNECT TYPE (P.910)

was changed from

BASIC

to

FULL

.

NETW DROP NUMBER

(P.900)

was changed.

Network Option cable connections are loose or not connected.

Network Option board failed or master communications failed.

F00014 REVERSED TACH

LEADS

The difference between the speed reference and speed feedback was
greater than

TACH LEAD FLT THRESH (P.227)

for the time

specified in

TACH LEAD FLT DELAY

(P.228)

.

Possible causes:

Tachometer or encoder leads are reversed.

The motor armature leads are reversed.

The motor field leads are reversed.

There is an overhauling load

The drive was not tuned properly.

F00015 INVERTING FAULT

AVOIDED

The inverting fault

avoidance logic has detected conditions that could

have caused an inverting fault. The drive took action to avoid an actual
inverting fault.

F00016 PHASE LOSS

PHASE LOSS DETECT EN

(P.609)

is set to

ENABLE

and the measured AC

line voltage fell below 75% of the value specified by

NOMINAL AC LINE

VOLTS (P.307).

F00017 kit missing or

unsupported kit
installed

The I/O Expansion board and Field Current Regulator are standard
equipment, and are required. The drive does not support the DeviceNet
kit.

F00030
to
F00041

SCR No. n
NOT OPERATING

The value of `n' indicates the SCR that is not operating;
n = 1-6, 11-16.

F00042 MULTIPLE SCRS

NOT OPERATING

One or more thyristor (SCR) is not carrying an equal load.
Possible causes:

Disconnected, loosely connected or damaged thyristor gating circuit.

Blown AC line fuse(s).

Improper current minor loop tuning.

Improper speed/voltage loop tuning.

Failed thyristor.

F00060 SELF TUNING

FAULT

Self Tune aborted by external input.
Possible causes:

Operator stop asserted.

Drive interlock(s) open.

Drive fault became active.