Use with DriveExecutive Software
PowerFlex 1203-USB Converter User Manual
Publication DRIVES-UM001D-EN-P
Both parameters should be incrementing and at approximately the same
values.
4. To clear the DF1 counters, set converter Parameter 03 - [Clear DF1
Counts] to ‘1’ (Clear Counts).
5. Press Enter.
Using RTU Master Mode for
a Serial Multi-drop Network
With the converter in RTU Master mode, you can monitor, configure, and
control up to 32 DSI drives.
Important: All PowerFlex 40 and PowerFlex 400 drives on an RTU Master
network must have an open internal Port 1. Thus, a
22-COMM-* adapter cannot be connected to this port via the
Internal Interface ribbon cable.
Important: All PowerFlex 520-Series drives on an RTU Master network
must not have a DSI communication option installed or
connected (only the 1203-USB converter can be connected).
When a drive faults in an RTU Master network, all other drives remain
operational and unaffected.
Network Wiring
See
for information on wiring an RTU Master
serial multi-drop network.
Establishing Communication
Establish communications between the drive connected to the 1203-USB
converter and the computer.
Configuring the Drive Parameters
See
Configuring the Drive Parameters on page 3-10
configure the drive parameters.
TIP: A total of 247 drives can be supported on the RTU Master network
when RS-485 repeaters are installed.